Ladder Logic
ILX34-AENWG ♦ Point I/O Platform
User Manual
Wireless POINT I/O Adapter
Page 132 of 177
ProSoft Technology, Inc.
August 16, 2013
Configuration Data
Data Type
Default Value
Valid Data Values
Sensor Type Channel 1
SINT
5
0=mV
1=B
2=C
3=E
4=J
5=K
6=N
7=R
8=S
9=T
Digital Filter Channel 1
INT
0
0…10,000 ms
Low Alarm Limit Channel 1
INT
-32,768
-32,768…32,767
High Alarm Limit Channel 1
INT
32,767
-32,768…32,767
Low Low Alarm Limit Channel 1
INT
-32,768
-32,768…32,767
High High Alarm Limit Channel 1
INT
32,767
-32,768…32,767
1734-IT2
1734 POINT I/O Catalog Number
RSLogix5000 Module Description
1734-IT2
2 Channel Thermocouple Input, Isol.
Configuration Data
Data Type
Default Value
Valid Data Values
Temperature Mode Channel 1
SINT
1
0=mV/Custom Scale
1=°C
2=°F
3=°K
4=°R
Cold Junction Enable Channel 1
SINT
1
0=Disabled
1=Enabled
Cold Junction Offset Channel 1
INT
0
0…7,000 (0.00…70.00)
Input Data
Data Type
Default Value
Valid Data Values
Data Channel 0
INT
0
-32,768…32,767
Data Channel 1
INT
0
-32,768…32,767
Status Byte Channel 0
SINT
0
Bit 0 Fault
Bit 1 Calibration
Bit 2 LowAlarm
Bit 3 HighAlarm
Bit 4 LowLowAlarm
Bit 5 HighHighAlarm
Bit 6 Underrange
Bit 7 Overrange