ProSoft Technology ILX34-AENWG User Manual
Page 148
Ladder Logic
ILX34-AENWG ♦ Point I/O Platform
User Manual
Wireless POINT I/O Adapter
Page 148 of 177
ProSoft Technology, Inc.
August 16, 2013
Configuration Data
Data Type
Default Value
Valid Data Values
Max Receive Characters
SINT
20
-128…+127 (0…128)
Receive Start Delimiter Mode
SINT
0
0=No Start Delimiter
1=Exclude Start Delimiter
2=Include Start Delimiter
Receive Start Delimiter Character
SINT
58
(0x3A)
Any Valid ASCII Character
(Default is Colon [:])
Receive Record End Mode
SINT
2
0=No End Delimiter
1=Exclude End Delimiter
2=Include End Delimiter
Receive End Delimiter
SINT
13
(0x0d)
Any Valid ASCII Character
(Default is Carr. Return)
Receive String Data Type
SINT
1
0=Array
1=Short String
2=String
Pad Mode
SINT
1
0=Pad Mode Disabled
1=Pad Mode Enabled
Pad Character
SINT
0
(0x00)
Any Valid ASCII Character
(Default is NULL)
Receive Swap Mode
SINT
0
0=Disabled
1=16-bit Swap Enabled
2=24-bit Swap Enabled
3=32-bit Swap Enabled
DeviceNet Handshake Mode
SINT
1
0=Master/Slave handshake
1=Produce Immediate
Max Transmit Characters
SINT
20
-128…+127 (0…128)
1734-232ASC
1734 POINT I/O Catalog Number
RSLogix5000 Module Description
1734-232ASC
1 Channel ASCII Interface Module
Configuration Data
Data Type
Default Value
Valid Data Values
Transmit End Delimiter Mode
SINT
2
0=No End Delimiter
1=Exclude End Delimiter
2=Include End Delimiter
Transmit End Delimiter Character
SINT
13
(0x0d)
Any Valid ASCII Character
(Default is Carr. Return)
Consume String Data Type
SINT
1
0=Array
1=Short String
2=String
Transmit Swap Mode
SINT
0
0=Disabled
1=16-bit Swap Enabled
2=24-bit Swap Enabled