ProSoft Technology ILX34-AENWG User Manual
Page 118
Ladder Logic
ILX34-AENWG ♦ Point I/O Platform
User Manual
Wireless POINT I/O Adapter
Page 118 of 177
ProSoft Technology, Inc.
August 16, 2013
2 In the edit window, change the value of the R
EAD
D
ATA
array from INT[600] to
INT[1000] as shown, and then click A
PPLY
.
Note: If RSLogix resets your data values, refer to the backup copy of your program to re-enter your
configuration parameters.
3 Next, navigate to C
ONTROLLER
T
AGS
and double click to open an edit
window. Click the M
ONITOR
T
AGS
tab at the bottom of the edit window.
4 Click [+] to expand the AENWG.CONFIG.M
OD
D
EF
section, and then change
the R
EAD
R
EG
C
NT
parameter from 600 to 1000.
5 Save and download the sample program to the processor.
6 Go Online with the ControlLogix processor, and then toggle the
AENWG.CONTROL.W
ARM
B
OOT
bit to download the configuration to the
ILX34-AENWG module.
Note: Any changes made to the AENWG.CONFIG or WriteData arrays must be downloaded to the
ILX34-AENWG module. The use of the AENWG.CONTROL.WarmBoot or
AENWG.CONTROL.ColdBoot bit will cause the ILX34-AENWG module to re- read the
configuration from the ControlLogix processor.
To modify the W
RITE
D
ATA
array, follow the steps in this topic, but substitute
W
RITE
D
ATA
for ReadData throughout. Also, make sure that the R
EAD
D
ATA
and
W
RITE
D
ATA
arrays do not overlap in the module memory. For example, if your
application requires 2000 words of WriteData starting at register 0, then your
AENWG.CONFIG.M
OD
D
EF
.R
EAD
S
TART
R
EG
must be set to a value of 2000 or
greater.
5.2
1734 POINT I/O Module/RSLogix 5000 Controller Tag Reference
Attention: You must use series C POINT I/O modules with the ILX34-AENWG adapter. Series A
or B POINT I/O modules will not work with this adapter.