ProSoft Technology ILX34-AENWG User Manual
Page 153
ILX34-AENWG ♦ Point I/O Platform
Reference
Wireless POINT I/O Adapter
User Manual
ProSoft Technology, Inc.
Page 153 of 177
August 16, 2013
Relative Humidity
5 to 95% noncondensing. IEC 60068-2-30
Shock
IEC 60068-2-27 30g operating 50g nonoperating
Vibration
IEC 60068-2-6 5g 10-500Hz
ESD Immunity
IEC 60068-4-2 6kV contact discharge 8kV
air discharge
Radiated RF Immunity
IEC 60068-4-3 10V/m 1kHz sine AM Modulation
30MHz to 2GHz
10V/m 200 Hz AM Pulse 50% to 100 % frequencies
EFT/B Immunity
IEC 61000-4-5 4kV at 5kHz power ports, 2kV 5.0kHz
communication ports
Surge Transient Immunity
IEC 61000-4-5
1kV line-line (DM) and 2kV line-earth (CM) on
comm. Ports
1kV line-line (DM) and 2kV line-earth (CM) on
power ports
Conducted RF Immunity
IEC 61000-4-6 10Vrms 1kHz sine 80% modulation
AM 150kHz to 80MHz
Emissions
CISPR 11 Group 1 Class A
Enclosure rating
None (open style)
Radio / RF
Communication standard
802.11g
Security
802.11i (WPA2)
Encryption
None, WEP, AES
RF Power
12 dBm (16 mW) without antenna gain
– allows up to
6 dBi antenna for ETSI, 100 mW EIRP
limited countries
Antenna connection
One RP-SMA connector
IGMP querying support
Use of WDS to support IGMP querying and multicast
Indoor distance
100 meters at 54 Mbps (use RadioLinx
®
Industrial
Hotspots radios to extend range)
Outdoor distance
Up to 3 km with high gain, directional antennas and
RF line-of-sight
Enclosure
Cover
Molded plastic, integrated DIN rail clip
All other components
Supplied by Rockwell Automation
®
standard
1734-AENTR parts
Enclosure rating
None (open style)