ProSoft Technology ILX34-AENWG User Manual
Page 128
Ladder Logic
ILX34-AENWG ♦ Point I/O Platform
User Manual
Wireless POINT I/O Adapter
Page 128 of 177
ProSoft Technology, Inc.
August 16, 2013
1734-IR2
1734 POINT I/O Catalog Number
RSLogix5000 Module Description
1734-IR2
2 Channel RTD Input
Configuration Data
Data Type
Default Value
Valid Data Values
Low Engineering Channel 0
INT
1,000
-32,768…32,767
High Engineering Channel 0
INT
5,000
-32,768…32,767
Digital Filter Channel 0
INT
0
0…10,000 ms
Low Alarm Limit Channel 0
INT
-32,768
-32,768…32,767
High Alarm Limit Channel 0
INT
32,767
-32,768…32,767
Low Low Alarm Limit Channel 0
INT
-32,768
-32,768…32,767
High High Alarm Limit Channel 0
INT
32,767
-32,768…32,767
Limit Alarm Latch Channel 0
SINT
0
0=No Latching
1=Alarms Latch
Alarm Disable Channel 0
SINT
0
0=Alarms Enabled
1=Alarms Disabled
Sensor Type Channel 0
SINT
1
0=Ohms
2=200
Pt
385
5=100
JPt
3916
6=200
JPt
3916
9=10
Cu
427
10=120
Ni
672
11=100
Ni
618
12=120
Ni
618
Temperature Mode Channel 0
SINT
1
0=Custom Scale
1=°C
2=°F
3=°K
4=°R
Low Engineering Channel 1
INT
1,000
-32,768…32,767
High Engineering Channel 1
INT
5,000
-32,768…32,767
Digital Filter Channel 1
INT
0
0…10,000 ms
Low Alarm Limit Channel 1
INT
-32,768
-32,768…32,767
High Alarm Limit Channel 1
INT
32,767
-32,768…32,767
Low Low Alarm Limit Channel 1
INT
-32,768
-32,768…32,767
High High Alarm Limit Channel 1
INT
32,767
-32,768…32,767
Limit Alarm Latch Channel 1
SINT
0
0=No Latching
1=Alarms Latch
Alarm Disable Channel 1
SINT
0
0=Alarms Enabled
1=Alarms Disabled