About the Example Applications
ILX34-AENWG ♦ Point I/O Platform
User Manual
Wireless POINT I/O Adapter
Page 56 of 177
ProSoft Technology, Inc.
August 16, 2013
Note: If you receive an error message during these steps, refer to your RSLogix documentation to
interpret and correct the error.
3.4.4 Verify the Chassis Size
You must configure the chassis size for the ILX34-AENWG before you can make
any I/O Configure Chassis Size (page 39). The default setting for the chassis
size is 1 slot, which represents the adapter by itself.
When the adapter's non-volatile chassis size does not match the actual number
of modules present on its backplane, the adapter does not make any I/O
connections and an error occurs, as shown in the M
ODULE
P
ROPERTIES
dialog
box.
This procedure synchronizes the chassis size value from the RSLogix 5000
software into the ILX34-AENWG hardware. You must be online to perform this
procedure.
1 Verify that RSLogix 5000 software is online to the processor.
2 Double-click the ILX34-AENWG
adapter under I/O
C
ONFIGURATION
in the
C
ONTROLLER
O
RGANIZATION
window. This action opens the M
ODULE
P
ROPERTIES
dialog box.
3 On the M
ODULE
P
ROPERTIES
dialog box, click the C
ONNECTION
tab. Notice
that the M
ODULE
F
AULT
area of the dialog box contains information about the
error code.