Ladder Logic
ILX34-AENWG ♦ Point I/O Platform
User Manual
Wireless POINT I/O Adapter
Page 138 of 177
ProSoft Technology, Inc.
August 16, 2013
Configuration Data
Data Type
Default Value
Valid Data Values
On Value 1
Off Value 1
On Value 2
Off Value 2
On Value 3
Off Value 3
On Value 4
Off Value 4
DINT
DINT
DINT
DINT
DINT
DINT
DINT
DINT
0
0
0
0
0
0
0
0
Counter Config 3, 5, 6, 7:
0…16,777,215
Counter Config 0, 1, 2, 4:
0 to Rollover Value
SS PWM Value
(<0 or >9500 =Hold Last State)
INT
0
0…9500
(0.00…95.00%)
SS Counter Control
SINT
0
SS Counter Reset
BIT 0
0=Count Unchanged
1=Count Cleared
SS Counter Preset
BIT 1
0=Count Unchanged
1=Count Set to Preset
SS Value Reset
(Stored / Accum. Count)
BIT 2
0=Count Unchanged
1=Count Cleared
1734-VHSC24, 1734-VHSC5
1734 POINT I/O Catalog Number
RSLogix5000 Module Description
1734-VHSC24
1 Channel 15…24V dc Very High-speed Counter
1734-VHSC5
1 Channel 5V dc Very High-speed Counter
Configuration Data
Data Type
Default Value
Valid Data Values
SS Output Control
SINT
0
SS Out 0 Force
BIT 0
0=Output Off
1=Output Forced On
SS Out 0 En
BIT 1
0=Output Disabled
1=Output Enabled
SS Out 0 Electronic Fuse
BIT 2
0=Auto Retry
1=Latch Off
SS Out 0 Diagnostic Speed
BIT 3
0 ≤ 8 ms Response
1=50 ms Response
SS Out 1 Force
BIT 4
0=Output Off
1=Output Forced On
SS Out 1 En
BIT 5
0=Output Disabled
1=Output Enabled
SS Out 1 Electronic Fuse
BIT 6
0=Auto Retry
1=Latch Off
SS Out 1 Diagnostic Speed
BIT 7
0 ≤ 8 ms Response
1=50 ms Response
To enter values from +128 to +255, use these conversion formulas:
Desired Decimal Position Value - 256 = Entered Decimal Position Value.
Example: for a divisor of 200, 200 - 256 = -56