ProSoft Technology ILX34-AENWG User Manual
Page 134
Ladder Logic
ILX34-AENWG ♦ Point I/O Platform
User Manual
Wireless POINT I/O Adapter
Page 134 of 177
ProSoft Technology, Inc.
August 16, 2013
Configuration Data
Data Type
Default Value
Valid Data Values
Low Limit Channel 1
INT
-32,768
-32,768…32,767
High Limit Channel 1
INT
32,767
-32,768…32,767
Range Type Channel 1
SINT
0
0=4…20 mA
2=0…20 mA
Fault Mode Channel 1
SINT
1
0=Hold Last State
1=Go to Low Clamp
2=Go to High Clamp
3=Go to Fault Value
1734-OE2C
1734 POINT I/O Catalog Number
RSLogix5000 Module Description
1734-OE2C
2 Channel Analog Current Output
Configuration Data
Data Type
Default Value
Valid Data Values
Idle Mode Channel 1
SINT
1
0=Hold Last State
1=Go to Low Clamp
2=Go to High Clamp
3=Go to Fault Value
Limit Alarm Latch Channel 1
SINT
0
0=No Latching
1=Alarms Latch
Alarm Disable Channel 1
SINT
0
0=Alarms Enabled
1=Alarms Disabled
Input Data
Data Type
Default Value
Valid Data Values
Status Byte Channel 0
SINT
0
Bit 0 Fault
Bit 1 Calibration
Bit 2 LowAlarm
Bit 3 HighAlarm
Status Byte Channel 1
SINT
0
Bit 0 Fault
Bit 1 Calibration
Bit 2 LowAlarm
Bit 3 HighAlarm
Output Data
Data Type
Default Value
Valid Data Values
Data Channel 0
INT
0
-32,768…32,767
Data Channel 1
INT
0
-32,768…32,767
1734-OE2V
1734 POINT I/O Catalog Number
RSLogix5000 Module Description
1734-OE2V
2 Channel Analog Voltage Output
Configuration Data
Data Type
Default Value
Valid Data Values
Fault Value Channel 0
INT
0
-32,768…32,767