ProSoft Technology ILX34-AENWG User Manual
Page 147
ILX34-AENWG ♦ Point I/O Platform
Ladder Logic
Wireless POINT I/O Adapter
User Manual
ProSoft Technology, Inc.
Page 147 of 177
August 16, 2013
Present / Latched Data
To interpret values from -2,147,483,648 to -1, use this conversion formula:
Stored Data Tag Value + 4,294,967,296 = Actual Stored Data Tag Value.
Example: for a read value of -1,794,967,296:
-1,794,967,296 + 4,294,967,296 = 2,500,000,000 actual value
1734-SSI
1734 POINT I/O Catalog Number
RSLogix5000 Module Description
1734-SSI
1 Channel Synchronous Serial Interface
Output Data
Data Type
Default Value
Valid Data Values
Control
SINT
0
Latch Acknowledge
BIT 0
0
0=Latch Not Cleared
1=Latch Cleared
Compare 0 Acknowledge
BIT 1
0
0=Compare0 Not Reset
1=Compare0 Reset
Compare 1 Acknowledge
BIT 2
0
0=Compare1 Not Reset
1=Compare1 Reset
Compare 0 Select
BIT 3
0
0=Compare0 Not Selected
1=Compare0 Selected
Compare 1 Select
BIT 4
0
0=Compare1 Not Selected
1=Compare1 Selected
1734-232ASC
1734 POINT I/O Catalog Number
RSLogix5000 Module Description
1734-232ASC
1 Channel ASCII Interface Module
Configuration Data
Data Type
Default Value
Valid Data Values
Serial Character Format
(ASCII Format:
Data Bits / Parity / Stop)
SINT
0
0=7N2
1=7E1
2=7O1
3=8N1
4=8N2
5=8E1
6=8O1
7=7E2
8=7O2
Serial Comm Speed
(Communication Rate of the Serial Port)
SINT
0
0=9600 Kbps
1=1200 Kbps
2=2400 Kbps
3=4800 Kbps
4=19.2 KBps
5=38.4 KBps