GT490X Engineer’s Reference Guide
Clearing ‘Test Fail’ Indication
If the display shows:-
The system has a zone On Test that has failed
when the system was Set.
Please note: we recommend that the Test Attribute
is only used on 12Hr type zones.
To clear the display proceed as follows.
1)
Enter the Engineer Code. The display will show:-
2)
Enter a valid User Code. The display will show:-
3)
Press No. The display will show:-
4)
Press Yes. The system will start to Set.
5)
Allow the system to fully Set.
6)
Enter the Engineer Code again to Unset the
system. The display will show:-
Unset Test Fail
01 Jan 00: 00: 01
01 Jan 00: 00: 01
Do you want to . .
Use ENGNR. Mode ?
Do you want to . .
SET the System ?
Enter Authorisor
Code . . . . . .