Reporting a Mains Fail on a PSU.

In order to report a Mains Fail on a PSU the Fault output on
the PSU would be wired to a Zone on the Control Panel.

The Zone Type would be programmed as ‘Fault’.

Program the Zone Descriptor as External PSU.

At the end of the Program Zones menu we have a menu called Program Events Tags,
enter this option and select the Zone number you have programmed as Fault.

Program the Tag as Mains Fail. Then program a Digi Channel as Mains Fail.

This will allow for full reporting of External PSUs.

Page

30

GT490X Engineer’s Reference Guide