GT490X Engineer’s Reference Guide
14)
Press No until the setting required for V.Min is
displayed then press Yes.
The display will show:-
15)
Press No until the required setting for On-Charge
Volts max (Battery) is displayed then press Yes.
The display will show:-
16)
Press No until the required setting for On-Charge
Volts min (Battery) is displayed then press Yes.
The display will show:-
17)
Press No until the required setting for Off-Charge
Volts max (Battery) is displayed then press Yes.
The display will show:-
18)
Press No until the required setting for Off-Charge
Volts min (Battery) is displayed then press Yes.
The display will show:-
19)
Press Yes. The display will show:-
20)
Press Yes. The display will show:-
PSU . . .
Diagnostics ?
PSU Test Time
= 01 Hrs
Change / List
Test Limits ?
On - Chg. max = 14.0
On - Chg. min = 12.6
Off - Chg. max = 14.0
Off - Chg. min = 12.6
Off - Chg. max = 14.0
Off - Chg. min > 12.6
On - Chg. max = 14.0
On - Chg. min > 12.6