Programming digicom / vo-comm off/on – RISCO Group Gardtec 490X User Manual
Page 49

Page
48
GT490X Engineer’s Reference Guide
Programming Digicom / Vo-Comm Off/On
Within this section we will program the Digicom and Modem. Both of these devices are
built on the main PCB of the control panel. Only the main functions will be covered
within this Step by Step section.
If required, the 5, 5, Yes, No default may be used to set the basic comms
configuration. When this default is used all other settings that have been
programmed will be returned to factory defaults. When this default is used the
following will be set.
Digicom Type
Mod+F/F
Modem Mode
No Return
This will allow for connection to GardTec Remote for programming functions.
1)
Enter into Engineer Mode
To do this follow Steps 1 to 4 on page 18
With the display showing:-
2)
Press No five times. The display will show:-
3)
Press Yes. The display will show:-
4)
Press Yes. The display will show:-
Digicom Types available are.
Mod+F/F
Modem enabled and Ademco Fast Format Central
Station protocol enabled.
Mod+SIA
Modem enabled and SIA Central Station protocol enabled.
Mod+PID
Modem enabled and Point ID Central Station protocol
enabled.
For programming details on PID (Point ID Protocol) and SIA please refer to page 91
Program . . . . _ _ _
Zones ?
Program . . . . _ _ _
Digicom ?
Program Digicom
Type or Test ?
Digicom Type . . . .
=Mod+F/F
PR5851 Rev12 490X Eng Ref Guide.qxd 10/05/2012 11:33 Page 48