RISCO Group Gardtec 490X User Manual
Page 84
Page
83
GT490X Engineer’s Reference Guide
Other BS8243 Notes to Consider
When a system auto re-arms with a zone in fault condition The GardTec control panel
will omit the zone concerned. A signal should be sent to the central station indicating
that a detector(s) has (have) been isolated. To achieve this a Digi channel should be
programmed as Zone Exclude, this will automatically send the required signal as the
detector is omitted.
Output Option (Status)
This option has three operating modes and is intended to provide a visual indication of
the system status.
System Set
Output On for 10 seconds
System Unset
Output On for 1s Output Off for 1s for a 10 second period
Confirmed Alarm Output On for 3 seconds Output Off for 1s until system reset.
It is envisaged that this status output would be fitted to an indicator (i.e. LED) that can
be seen from outside the premises.
PR5851 Rev12 490X Eng Ref Guide.qxd 10/05/2012 11:33 Page 83