Page 64: Table 4.6, Preset single and multiple registers, Table 4.7, Response sample

background image

64

Wi-MGR User Guide

800.518.1519

4

4.2.3 Function 06: Preset Single Register & Function 16:

Preset Multiple Registers

To set the relay outputs over Modbus, first set the relay activation mode must be set to Modbus

only. Do this in the web interface, at the bottom of the Digital IO Configuration page - Chapter

3, “Digital IO Configuration Page” on page 42. The master must then send a Preset Single or

Preset Multiple Register request packet.

4.3. RTU

Framing

The example below shows a typical Query/Response from a Wi-MGR.

Slave address 2 responds to Function Code 4 with six bytes of hexadecimal data and ends with

CRC16 checksum.

Register Values:

40001 = 0000 (hex)

40002 = 0000 (hex)

40003 = 0001 (hex)

Register

Name

Description

Units

Range

30001

Digital Input 1

Digital Input 1: 1=0, 0=off

uint16

0-1

30002

Digital Input 2

Digital Input 2: 1=0, 0=off

uint16

0-1

30003

Digital Input 3

Digital Input 3: 1=0, 0=off

uint16

0-1

30004

Digital Input 4

Digital Input 4: 1=0, 0=off

uint16

0-1

Table 4.5

Read Input Registers

Register

Name

Description

Units

Range

49001

Relay K1

Relay 1 Activation: 1=active,

0=inactive

uint16

0-1

49002

Relay K2

Relay 2 Activation: 1=active,

0=inactive

uint16

0-1

Table 4.6

Preset Single and Multiple Registers

Slave

Address

Function

Code

Count Bytes

of Data

Register

Data

Msb Lsb

Register

Data

Msb Lsb

Register

Data

Msb Lsb

CRC 16

“Lsb”

CRC 16

“Msb”

02

04

06

00 00 00 00 00 01 B5

A3

Table 4.7 Response Sample