RLE Wi-MGR V.1.6 User Manual

Page 57

background image

rletech.com

Wi-MGR User Guide

57

3

Web Interface

EIA-485 Slave

Address

Set a RTU address from 1-254. If the field is left at 0, there is no

transmission on the EIA-485 port.

Default: 0 (disabled)

Modbus

Modbus/TCP/UDP

Slave Unit Identifier

This designator is used for Modbus RTU over an Ethernet

connection. The default slave unit identifier is 0, which disables this

feature.

To enable this option, enter a TCP/UDP slave address from 1-254 in

this field. In most instances, the identifier is typically set at 1.

Default: 0 (disabled)

Bacnet

Device ID

Assign a name to uniquely identify each BACnet device on the

network, up to 30 characters. 0 = disabled

Device Name

Assign a name - up to 38 characters - to the unit for BACnet

discovery/integration.

Description

Add any additional details about the device, up to 38 characters.

UDP Port

Enter a 0 to specify port 47808 (0xBAC0) as the UDP port. If another

port is specified by your application, enter that value here.

Default setting: 0

Bacnet Pics

Click this link to view the Bacnet identifiers and objects supported by

the Wi-MGR

Register as Foreign

Device at IP

IP address of the master device with which you’re trying to

communicate. Requires a BBMD for foreign device discovery.

Registration Time-

to-Live

Time, in seconds, for foreign device discovery.

BBMD Data

The values in the broadcast distribution table represent IP addresses

and masks. Shown here for reference, the values are editable via

BACnet.

Option

Description

Table 3.12

Com Port1/Modbus/Bacnet Options