Web Interface
EIA-485 Slave
Address
Set a RTU address from 1-254. If the field is left at 0, there is no
transmission on the EIA-485 port.
Default: 0 (disabled)
Modbus
Modbus/TCP/UDP
Slave Unit Identifier
This designator is used for Modbus RTU over an Ethernet
connection. The default slave unit identifier is 0, which disables this
feature.
To enable this option, enter a TCP/UDP slave address from 1-254 in
this field. In most instances, the identifier is typically set at 1.
Default: 0 (disabled)
Bacnet
Device ID
Assign a name to uniquely identify each BACnet device on the
network, up to 30 characters. 0 = disabled
Device Name
Assign a name - up to 38 characters - to the unit for BACnet
discovery/integration.
Description
Add any additional details about the device, up to 38 characters.
UDP Port
Enter a 0 to specify port 47808 (0xBAC0) as the UDP port. If another
port is specified by your application, enter that value here.
Default setting: 0
Bacnet Pics
Click this link to view the Bacnet identifiers and objects supported by
the Wi-MGR
Register as Foreign
Device at IP
IP address of the master device with which you’re trying to
communicate. Requires a BBMD for foreign device discovery.
Registration Time-
to-Live
Time, in seconds, for foreign device discovery.
BBMD Data
The values in the broadcast distribution table represent IP addresses
and masks. Shown here for reference, the values are editable via
BACnet.
Option
Description
Table 3.12
Com Port1/Modbus/Bacnet Options