Table 3.5, Digital io configuration options – RLE Wi-MGR V.1.6 User Manual

Page 43

background image

rletech.com

Wi-MGR User Guide

43

3

Web Interface

Option

Description

Digital IO

Enable or disable the digital inputs and relay outputs. If there are no

digital inputs and relay outputs installed on your Wi-MGR, select

Not Installed.

Default: Enabled

Digital Inputs #1, #2, #3, and #4
Each digital input has its own configurable options, but all fields have several read-only

values that are displayed. These fields include the input’s modbus register number, the

input’s bacnet instance, and the input’s status information.

Adjust the following editable fields as necessary:

Input Type

Decide if the point should go into alarm or simply report its status.

Default: Alarm

Polarity

Note the polarity of the input, normal or reversed.

Default: Normal

Active Text

This text will appear on the Wi-MGR’s home page when the input

goes into an alarm condition.

Default: #a, where # represents the digital input number

Inactive Text

This text will appear on the Wi-MGR’s home page when the input is

in its normal operating condition.

Default: #i, where # represents the digital input number

Alarm Delay

The number of seconds that passes between the time the point

goes into an alarm state and the time that alarm is annunciated.

Default: 0

Active Relay

Designate which relay outputs are activated when the point goes

into alarm.

Select: None, K1, K2, or K1+K2

Default: None

Table 3.5

Digital IO Configuration Options