2 eia-232 com connection, 3 modbus eia-485 connections, Eia-232 com connection modbus eia-485 connections – RLE Wi-MGR V.1.6 User Manual
Page 16: Figure 2.5, Eia-232 com connection, Figure 2.6, Eia-485 connection

16
Wi-MGR User Guide
800.815.1519
2
Getting Started
2.3.2 EIA-232
COM
Connection
The Wi-MGR can be connected directly to a PC through its EIA-232 port. This is useful for IP
configuration, firmware downloads, and troubleshooting. The EIA-232 connection is only
used as a temporary connection. Connect the straight through, 9-pin serial cable as shown in
Figure 2.5
EIA-232 COM Connection
2.3.3 Modbus
EIA-485
Connections
The Wi-MGR can function as a Modbus Slave over an EIA-485, 2-wire hardware connection,
as shown in Figure 2.6.
Figure 2.6
EIA-485 Connection