2 function 04: read input registers, Function 04: read input registers, Table 4.3 – RLE Wi-MGR V.1.6 User Manual
Page 63: Read output registers, Table 4.4, Read input registers packet structure

rletech.com
Wi-MGR User Guide
63
4
4.2.2 Function 04: Read Input Registers
To read the Wi-MGR’s input values, the master must send a Read Input Registers request
packet.
The Read Intput Registers request packet specifies a start register and the number of registers
to read. The start register is numbered from zero (30001 = zero, 30002 = one, etc.).
Register
Name
Description
Units
Range
40001
Id
Sensor Identification number
uint16
0-65535
40002
Out Of Service
Shows when the sensor is in
maintenance mode or offline
uint16
0-65535
40003
Serial #
Wireless sensor serial number uint16x4
0-65535
40007
Raw Data #1
First data value displayed by
sensor
Unsigned 32 bit
integer
0-4294967295
40009
Raw Data #2
Second data value displayed
by sensor
Unsigned 32 bit
integer
0-4294967295
40011
Raw Data #3
Third data value displayed by
sensor
Unsigned 32 bit
integer
0-4294967295
40013
Converted Data #1
First data value converted by
the Wi-MGR
Unsigned 32 bit
integer
0-4294967295
40015
Converted Data #2
Second data value converted
by the Wi-MGR
Unsigned 32 bit
integer
0-4294967295
40017
Converted Data #3
Third data value converted by
the Wi-MGR
Unsigned 32 bit
integer
0-4294967295
40019
Age
Time since last transmission
received
Unsigned 32 bit
integer
0-4294967295
48001
Offline Delay
Time till the sensor reads
offline
uint16
0-65535
Table 4.3
Read Output Registers
Read Registers Request Packet
Read Registers Response Packet
Slave Address (1 byte)
Slave Address (1 byte)
04 (Function code) (1 byte)
04 (Function code) (1 byte)
Start Register (2 bytes)
Byte count (1 byte)
# of registers to read (2 bytes)
First register (2 bytes)
Crc Checksum (2 bytes)
Second register (2 bytes)
…
Crc Checksum (2 bytes)
Table 4.4
Read Input Registers Packet Structure