2.1. Installation
The Wi-MGR comes with two brackets that, when attached to the device, allow it to be
mounted in a 19-inch rack. Remove the screws from the side of the device, put the brackets in
place, and reapply the screws. Mount the device in a rack. Use the proper anchoring method to
mount the unit securely.
2.2. Wiring
2.2.1 Power Supply and Ground Connections
RLE Technologies recommends powering the Wi-MGR from a UPS supply so the device can
send alarm notifications during a power outage. The device can be powered through either the
jack or the power supply terminal block.
1
Connect an 18AWG ground wire from the ground terminal to a suitable earth ground.
2
Plug the provided wall adapter into the jack at P1 and a UPS outlet. The wall adapter has a
five foot (1.524m) power cord.
3
If you’re providing your own power supply, connect 24VDC to the unit through the power
terminal block.