Power
85-264VAC @ 500mA max, 50/60Hz
Inputs
Water Leak Detection Cable
Supplied with 15’ (4.57m) leader cable
Maximum
Length
5,000’ (1,524m)
Detection
Accuracy
± 2ft (0.6m)+ 0.5% of the cable length
Detection
Repeatability
± 2ft (0.6m) + 0.25% of the cable length
Detection Response Time
20-3600sec, software adjustable in 10sec
increments; ±2sec
Outputs
Analog
4-20mA Loop Powered, 18-36VDC, R
L
= 500Ω
max.
Relay
2 Form C Leak Relays, 2 Form C Cable Break
Relays; 1A @ 24VDC, 0.5A resistive @ 120VAC;
configurable for supervised or non-supervised,
latched or non-latched
Communications Ports
RS-232
1200, 2400, 9600 or 19200 baud (selectable);
No parity, 8 data bits, 1 stop bit
RS-485
1200, 2400, 9600 or 19200 baud (selectable);
No parity, 8 data bits, 1 stop bit
Protocols
Terminal
Emulation
(RS-232)
VT100 compatible
Modbus
(RS-485)
Slave; RTU Mode; Supports function codes 03, 04,
06 and 16
Alarm Notification
Audible
Alarm
85DBA @ 2’ (0.6m); re-sound 0-999min
Logging Capabilities
Event
Log
Last 512 events
Trend
Log
Cable current level every day, for the last 288 days
Login Security
Terminal Emulation Access
1 Administrator (password for configuration)
Display
Access
1 Administrator (password for configuration, no
password required to view panel status)
Front Panel Interface
Display
Text, 4x20 character backlit LCD, 0.60” (15.24mm)
character height, contrast adjustment
Push
Buttons
+, -, right, left, enter, escape
LED
Indicators
1 bi-color Power/Status (green=power on,
red=alarm)
Operating Environment
Temperature
Humidity
Altitude
32° to 122°F (0° to 50°C)
5% to 95% RH, non-condensing
10,000’ (3,048 meters) max.
Storage Environment
-4° to 158°F (-20° to 70°C)
Dimensions
12.0”W x 14.0”H x 4.0”D
(305mmW x 356mmH x 101mmD)
Weight
12 lbs. (5.45kg)
Mounting
Vertical wall mount or Vertical flush mount (kit
optional)
Certifications
CE; ETL listed: conforms to UL STD 61010A-1,
EN STD 61010-1; CAN/CSA C22.2 STD NO.
1010-02