User Guide: LD5000

Chapter 11: RS-232 Function Commands

www.rletech.com 970.484.6510

27

CHAPTER 11: RS-232 FUNCTION COMMANDS

11-1 SC - SYSTEM CONFIGURATION

Please see page 33 for more information about System Configuration options.

11-2 LS - LEAK STATUS

Menu selection LS displays the current leak status.

11-3 CA - CURRENT ALARMS

Menu selection CA displays the current alarm status.

** LD5000 Help **
SC – LD5000 System Configuration
LS - Leak Status
SL - Silence Leak Relay
SF - Silence Fault Relay
SR - Silence All Relays
CA - Current Alarms
RA - Reset Alarms
UP - Update Alarms
AS - Alarm Silence (LCD)
AH - Alarm History
CH - Clear Alarm History
TD - Trend Data Table (Leakage Current)
CT - Clear Trend Data Table
TI - Display Date/Time
NS - Network Status (RS-485/Modbus)
MR - Reset Modbus Status (RS-485)
ND - Network Display (RS-485)
MT - Modbus Display
EX - Exit

CA
LD5000
03/14/05 14:02:30 Leak Detected at 701ft

** LD5000 Help **
SC – LD5000 System Configuration
LS - Leak Status
SL - Silence Leak Relay
SF - Silence Fault Relay
SR - Silence All Relays
CA - Current Alarms
RA - Reset Alarms
UP - Update Alarms
AS - Alarm Silence (LCD)
AH - Alarm History
CH - Clear Alarm History
TD - Trend Data Table (Leakage Current)
CT - Clear Trend Data Table
TI - Display Date/Time
NS - Network Status (RS-485/Modbus)
MR - Reset Modbus Status (RS-485)
ND - Network Display (RS-485)
MT - Modbus Display
EX - Exit

LS

Cable Length: 4995ft
Sense Cable Current: 0uA
No Leak!