The Setup Menu allows authorized users to configure the LD5000’s settings. This menu is described in
greater detail in Chapter 7: LCD Setup Menu. Press the Esc key to exit the Setup Menu and return to the
Main Menu.
6-3
LOG/DATA
The Log/Data option displays the Log/Data Menu. This menu provides a view of the History Log and the
Trend Data and an option to clear both the History Log and the compiled Trend Data.
6-3.1 History Log
The History Log displays the most recent 100 events recorded by the unit. Events are displayed in the
following manner:
Number-Status-Description
Date Time whereas:
Number is a sequential event number assigned to the event.
Status is R = Returned to normal, A = Alarm, or F = Forced to Normal.
Description is a detail of the nature of the event.
Date is the date the event occurred.
Time is the time at which the event occurred.
6-3.2 Trend Data
The Trend Data displays the leakage current on the cable. One measurement is taken at the user set interval
(1 min - 1440 min; factory default is 1440 min (1day)). The log retains the 288 most recent entries.
Analyzing the Trend Data can help determine the location of long term contamination build up
(degradation), etc. on the cable. Press the Esc key to exit the Log/Data Menu and return to the Main Menu.
Trend Data: 2/4
TD002-Leakage=0uA
01/11/01 16:02:56
Down ->Up
Trend Data: 1/4
TD001-Leakage=0uA
01/10/01 16:02:56
Down ->Up
Alarm Log: 21/23
021-A-Leak @ 55ft
01/10/01 10:15:27
Down ->Up
Alarm Log: 23/23
023-R-System Booted
01/10/01 09:54:11
->Down Up
** Log/Data Menu **
History ->Trend
HistClr TrendClr
->Up
** Log/Data Menu **
-> History
Trend
HistClr TrendClr
TrndIntv
** Setup Menu **
->TripPoints Clock
Re-Alarm Ft/M
Calibrate FcDft
Enter Password:
0000
^