User Guide: LD5000

Chapter 12: System Configuration

www.rletech.com 970.484.6510

41

12-9.1 Display Mapping Results - 1

Option 1 displays the existing map.







** LD5000 Help **
SC – LD5000 System Configuration
LS - Leak Status
SL - Silence Leak Relay
SF - Silence Fault Relay
SR - Silence All Relays
CA - Current Alarms
RA - Reset Alarms
UP - Update Alarms
AS - Alarm Silence (LCD)
AH - Alarm History
CH - Clear Alarm History
TD - Trend Data Table (Leakage Current)
CT - Clear Trend Data Table
TI - Display Date/Time
NS - Network Status (RS-485/Modbus)
MR - Reset Modbus Status (RS-485)
ND - Network Display (RS-485)
MT - Modbus Display
EX - Exit

SC
LD5000 System Configuration Menu
1. System Name: LD5000
2. Clock: 01/05/01 14:54:29
3. RS-485 Baud: 9600
4. Relays
5. Cable Feet/Meters: (Feet)
6. Calibration
7. LCD Setup
8. Diagnostics
9. Mapping Mode
10. Exit
Enter Menu Selection >

Enter Menu Selection >9
LD5000 Mapping Mode Menu
1. Display Mapping Results
2. Begin Mapping
3. Exit
Enter Menu Selection >

NOTE:

When additional cable is added to the system or if cable is replaced, the
system should always be checked and remapped if necessary.

Enter Menu Selection >1

Mapping Data

Pnt#1 = 68ft; Pnt#2 = 176ft; Pnt#3 = 247ft;
Pnt#4 = 378ft; Pnt#5 = 494ft; Pnt#6 = 675ft


End of Mapping Data