Chapter 12: System Configuration
www.rletech.com 970.484.6510
35
12-4 RELAYS - 4
Menu selection 4 displays the Relay Configuration Menu. Output relays are configured from this menu.
12-4.1 Supervised On/Off - 1
Option 1 allows a user to turn the relay supervision on or off. If the relay is set as supervised, the relay will
be closed as long as no alarm condition exists. A leak, cable trouble, or a power failure will cause the relay
to open. Set the relay to unsupervised (normally open - NO).
** LD5000 Help **
SC – LD5000 System Configuration
LS - Leak Status
SL - Silence Leak Relay
SF - Silence Fault Relay
SR - Silence All Relays
CA - Current Alarms
RA - Reset Alarms
UP - Update Alarms
AS - Alarm Silence (LCD)
AH - Alarm History
CH - Clear Alarm History
TD - Trend Data Table (Leakage Current)
CT - Clear Trend Data Table
TI - Display Date/Time
NS - Network Status (RS-485/Modbus)
MR - Reset Modbus Status (RS-485)
ND - Network Display (RS-485)
MT - Modbus Display
EX - Exit
SC
LD5000 System Configuration Menu
1. System Name: LD5000
2. Clock: 01/05/01 14:54:29
3. RS-485 Baud: 9600
4. Relays
5. Cable Feet/Meters: (Feet)
6. Calibration
7. LCD Setup
8. Diagnostics
9. Mapping Mode
10. Exit
Enter Menu Selection >
Enter Menu Selection >4
LD5000 Relay Menu
1. Supervised On/Off (Off)
2. Latched On/Off (Off)
3. Silence Leak Relay (K1)
4. Silence Fault Relay (K2)
5. Reset Relays
6. Exit
Enter Menu Selection >
** LD5000 Help **
SC – LD5000 System Configuration
LS - Leak Status
SL - Silence Leak Relay
SF - Silence Fault Relay
SR - Silence All Relays
CA - Current Alarms
RA - Reset Alarms
UP - Update Alarms
AS - Alarm Silence (LCD)
AH - Alarm History
CH - Clear Alarm History
TD - Trend Data Table (Leakage Current)
CT - Clear Trend Data Table
TI - Display Date/Time
NS - Network Status (RS-485/Modbus)
MR - Reset Modbus Status (RS-485)
ND - Network Display (RS-485)
MT - Modbus Display
EX - Exit
SC
LD5000 System Configuration Menu
1. System Name: LD5000
2. Clock: 01/05/01 14:54:29
3. RS-485 Baud: 9600
4. Relays
5. Cable Feet/Meters: (Feet)
6. Calibration
7. LCD Setup
8. Diagnostics
9. Mapping Mode
10. Exit
Enter Menu Selection >
Enter Menu Selection >4
LD5000 Relay Menu
1. Supervised On/Off (Off)
2. Latched On/Off (Off)
3. Silence Leak Relay (K1)
4. Silence Fault Relay (K2)
5. Reset Relays
6. Exit
Enter Menu Selection >
Enter Menu Selection >1
Relay Supervise Mode ‘ON’ or ‘OFF’ (Off) >off
OK
LD5000 Relay Menu