Chapter 7: LCD Setup Menu
User Guide: LD5000
18 970.484.6510
www.rletech.com
CHAPTER 7: LCD SETUP MENU
The Setup Menu allows authorized users to adjust the LD5000’s settings. Each menu option displays a
different adjustable parameter. Press Esc to exit the Setup Menu and return to the Main Menu.
7-1
TRIPPOINTS
The TripPoints option allows users to modify the detection and contamination trip points for the LD5000.
These trip points help the system avoid false alarm readings. Throughout this menu, the user can also set
the leak alarm and contamination alarm delays (20 to 3600 seconds). Press Esc to exit the TripPoint Menu
and return to the Setup Menu.
7-2
CLOCK
OPTION
The Clock option allows users to modify the LD5000’s date and time settings. Press Esc to exit the Set
Clock function and return to the Setup Menu.
7-3
RE-ALARM
The Re-Alarm option allows users to determine the number of minutes between annunciations of the same
alarm. Enter 000 to disable this feature. Factory default is “0” (disabled). Press Esc to exit and return to
the Setup Menu.
Set Clock:
01/10/01 10:51
^ ^
Modify Contamination
TripPoint: 050 uA
Modify Detection
TripPoint: 150 uA
Modify Contamination
Alarm Delay:
120
Seconds
+/- then (Enter)
Modify Leak Alarm
Delay:
20
Seconds
+/- then (Enter)
** TripPoint Menu **
Leak LeakDelay
->Contam ContDelay
** TripPoint Menu **
->Leak LeakDelay
Contam ContDelay
** Setup Menu **
->TripPoints Clock
Re-Alarm Ft/M
Calibrate FcDft