Appendix A: Modbus Communication

User Guide: LD5000

74 970.484.6510

www.rletech.com

A-4

RTU FRAMING

The example below shows a typical Query/Response from a LD5000 module.

Table 11: Query Sample

Slave

Address

Function

Code

Count

Bytes of

Data

Register

Data

Msb Lsb

Register

Data

Msb Lsb

Register

Data

Msb Lsb

CRC 16

“Lsb”

CRC

16”Msb”

02

04

06

00 00 00 00 00 01

B5

A3

Table 12: Response Sample

Slave

Address

Function

Code

Count

Bytes of

Data

Register

Data

Msb Lsb

Register

Data

Msb Lsb

Register

Data

Msb Lsb

CRC 16

“Lsb”

CRC

16”Msb”

02

04

06

00 00 00 00 00 01

B5

A3


• Slave address 2 responds to Function Code 4 with 6 bytes of hexadecimal data and ends with CRC16 checksum.


Register Values:


40001 = 0000 (hex)
40002 = 0000 (hex)
40003 = 0001 (hex)



A-5

LD5000 LCD MODBUS STATUS SCREEN (COMMS)


Adr:xxx - The Modbus slave address set by the dip switch #1

9600b - The current baud rate of the Modbus RS-485 port

4in:xxxxx out:xxxxx - The number of RS-485 bytes received and transmitted

Min:xxxxx out:xxxxx - The number of Modbus packets received and transmitted

RESET - Press the Enter (

) key to reset the Modbus counters

Modbus Adr:002 9600b
4in:18234 out:12214
Min:3345 out:2121
->RESET