12-9.2 Begin Mapping - 2

Menu selection 2 begins the mapping process. Physically identify and mark points on the floor map. The
points should be easily accessible and somewhat evenly spaced. Number the points and record their
location (their distance from the control panel) on the reference map.

Short the cable at these points using a damp paper towel or sponge. Once you short a point, wait for the
leak to be detected - annunciated by a long (3 second) beep. Remove the short and wait for the all clear
signal - annunciated by a short (1 second) beep.

Mark the points on the reference map with the distances as measured by the LD5000. Once the cable is
mapped, select option 1 from the Mapping Mode Menu to view the new map.

** LD5000 Help **
SC – LD5000 System Configuration
LS - Leak Status
SL - Silence Leak Relay
SF - Silence Fault Relay
SR - Silence All Relays
CA - Current Alarms
RA - Reset Alarms
UP - Update Alarms
AS - Alarm Silence (LCD)
AH - Alarm History
CH - Clear Alarm History
TD - Trend Data Table (Leakage Current)
CT - Clear Trend Data Table
TI - Display Date/Time
NS - Network Status (RS-485/Modbus)
MR - Reset Modbus Status (RS-485)
ND - Network Display (RS-485)
MT - Modbus Display
EX - Exit

SC
LD5000 System Configuration Menu
1. System Name: LD5000
2. Clock: 01/05/01 14:54:29
3. RS-485 Baud: 9600
4. Relays
5. Cable Feet/Meters: (Feet)
6. Calibration
7. LCD Setup
8. Diagnostics
9. Mapping Mode
10. Exit
Enter Menu Selection >

Enter Menu Selection >9
LD5000 Mapping Mode Menu
1. Display Mapping Results
2. Begin Mapping
3. Exit
Enter Menu Selection >

Enter Menu Selection >2

Mapping Cable - Begin Mapping Points
Press any Key to End
Point #1 Distance = 50ft

Point #2 Distance = 29ft

Point #3 Distance = 22ft

Point #4 Distance = 4ft

Mapping Mode Off