Display

Fault description/note

E 51

Notice that annual maintenance is needed

E 54

Message: “Heat pump fault”.The flow monitor has tripped. A flow problem has occurred.

Possible causes are air in the system, a clogged dirt trap or a defect of the charging pump in

the indoor module. If the red indicator lamp illuminates, there is a problem in the outdoor

module which can only be remedied through customer service.

E 55

“Power company shut-off” message. Information that the power company has begun an

off-period. The heating pump is switched off. The second heating appliance is switched on

as necessary. The electrical heating must be locked on-site using a relay switch.

E 69

Failure or short in supply sensor HK2 (mixing circuit). Sensor F5

E 70

Failure or short inlet pipe WP Multi-purpose sensor 1 Sensor F11

E 71

Failure or short in lower buffer sensor Sensor F12

E 75

Failure or short, external sensor Sensor F9

E 76

Failure or short, domestic water sensor Sensor F6

E 78

Failure or short, collector sensor Sensor F8

E 80

Failure or short, room sensor heating circuit 1. No assignment by REMKO

E 81

EEPROM error. The valid value has been replaced by the default value. Check parameter

values!

E 90

Address 0 and 1 on bus. Bus codes 0 and 1 may not be used simultaneously.

E 91

Bus code assigned. The set bus code is already being used by another device.

E 135

Failure or short, lower WW buffer sensor, multifunction sensor 2. No assignment by REMKO

E 137

Failure or short in collector sensor 1, multifunction sensor 4. Sensor F14

E 140

Failure or short in return line (cooling-mode control sensor) Sensor F17

E 200 - E 207

Communication heating appliance 1 to WE 7

E 220 - E 253

Communication BM 0 to BM 15

E 240

Communication Manager

E 241

Communication (individual) heating appliances

E 242

Communication mixer

E 243

Communication Solar

Heat pump manager error
codes

The error codes listed in the table
can be called up in the display
of the heat pump manager. See

Controller ---> Displays --->
System ---> Errors. If an error with
a corresponding code is present,
an error scan can be performed by
pressing the assigned function key.
After a short period of time the 10

most recent faults, including the
date and time, are listed with the
exception of error codes 54 and
55. They are treated as recurring
messages and are not listed in the
error scan.