REMKO Multi-talent User Manual
Page 39
Heating circuit 1/2
Designation
Value range
Factory setting
Description
HC function
Standard
T-supply const
Swimming pool
(HC2)
WW(HC2)
Return(HC2)
Standard
Setting the function for the respective heating circuit.
• Standard (weather managed target temperature regulation
using heating curves).
• T-supply const (control in accordance with fixed supply
temperatures).
During heating periods (see time programme
heating
circuit 1/2 prog 1/2) the heating circuit is operated with the
set fixed supply temperature T-supply const T, during reduc-
tion periods correspondingly with the set fixed supply tem-
perature T-supply const N (see user
heating circuit 1/2
T-supply const T/N).
• Swimming pool (swimming pool regulation, only for heat-
ing circuit 2).
• WW (hot water circuit).
The supply sensor for heating circuit 2 is located in the hot
water tank [sensor 05].
The target value for the hot water temperature can be en-
tered under user
hot water
T-WW target 1/2/3.
The heating programme for the heating circuit functions as
an enabling programme for the tank.
During the reduction period, the tank's target temperature is
set to 10°C.
The heat generator controller's hot water priority function
can be used (see specialist
hot water
PPL).
• Return (return riser above mixer, only for heating circuit 2)
- not relevant for REMKO.
The supply sensor for the heating circuit is used as the return
sensor for the heat generator [sensor 11/05].
The mixer regulates 24h based on the heating circuit's set
value, Min T-supply.
Installation note:
Mixer Open: The heat generators supply is fed into the
return (return riser) (circulation must be ensured by the heat
generator).
Mixer Closed: Return for the heating circuits is piped.
The parameters for this level change in accordance with the function selected for the heating circuit.
Depending on the heating circuit, the values that can be adjusted here can vary.
Level 4 - SPECIALIST - Description of parameters and settings - continued
39