REMKO HEAT PUMP MANAGER
Designation
Value range
Factory setting
Description
WE 2 tank
(continued)
00-03
00
Switching characteristics:
The pump switches on if the temperature of the solid fuel
boiler T-WE 2 exceeds the temperature of the reference sen-
sor [sensor 12] in the amount of the hysteresis [Hyst burner
2+5K].
It shuts off if the temperature T-WE 2 falls below this
switch on temperature by 5K,
Start-up release:
It shuts off if the temperature for the solid fuel boiler T-WE 2 falls
below the temperature limit Min T-WE 2 (see specialist
heat-
ing appliance) by 5K.
The pump is enabled again if the tempera-
ture T-WE 2 rises above the set temperature limit Min T-WE 2.
WE 3 type
(Output A8
enable 2nd heating
appliance)
00-09
01
• 00 = No third heating appliance (multi-function MF 1).
• 01 = Single stage heating appliance (switching).
• 07 = Heat pump.
• 08 = Cooling 1.
• 09 = Cooling 2.
WE 4 type
(Output A9
Charging pump
indoor unit)
00-09
00
• 00 = No fourth heating appliance (multi-function MF 2).
• 01 = Single stage heat generator (switching).
• 07 = Heat pump.
• 08 = Cooling 1.
• 09 = Cooling 2.
Buffer type
0 0 - 0 2
0 0
Setting the tank type for the heating buffer.
• 00 = no buffer tank for heating operation.
• 01 = Buffer tank for heating operation [sensors 02, 03].
The activation of the heat generator 1 takes place with ref-
erence to sensor buffer top [sensor 03].
The charge pump lock impacts the sensor
Buffer top.
WW-charge pump ON: Buffer top > T-WW+5K hysteresis.
WW-charge pump ON: Buffer top < T-WW.
• 02 = Combination tank for heating and hot water operation.
The activation of the heat generator 1 takes place with ref-
erence to sensor buffer middle [sensor 02].
WW-charge pump ON: T-collector > T-WW+5K hysteresis.
WW-charge pump ON: T-collector < T-WW.
Configuration - continued
Level 4 - SPECIALIST - Description of parameters and settings - continued
28