Designation

Value range

Factory setting

Description

Min T-supply

10.0°C-110.0°C

18.0°C

Setting the minimum supply temperature for the selected
heating circuit.

T-supply cooling

Off/Closed

10°C-25°C

Off

Setting the supply temperature in cooling mode.

In the operating mode cooling, the temperature set here
might possibly be tuned by means of a mixer.

Off = This heating circuit does not cool
(Mixer Closed, pump Off).

Closed = mixer as bypass valve (mixer Closed, pump On).

T-frost protection

Off

-15.0°C-5.0°C

5.0°C

Setting the frost protection temperature.

If the outdoor temperature falls below the temperature set
here, the system switches into frost protection mode (pumps
switch on)

At "Off", the frost protection function is activated.

T-external delay

00:00-24:00

01:00

Setting the outdoor temperature delay

The type of outdoor temperature delay selected must take
the building design into account.
Because a change in outdoor temperature impacts the room
temperature later for a building with a heavy design (thick
walls), a long delay must be selected.
For a light design (in which the walls do not store heat) the
delay should be set to 0 hours.

Curve displacement

0.0K-50.0 K

0.0K

Setting the heating curve distance.

The calculated target temperature for the heating circuit is
increased by the value set here.

The heating curve distance equalises sensor tolerances and
heat losses up to the mixer.

Demand require-
ment

On / Off

Off

The heating circuit can be used with superior functions
(e.g. emergency cooling of a heating appliance to protect
against overheating; heat dissipation in service mode) as
a heat sink/consumer (= ON).
For the duration of the function, the heating circuit is heated
with the maximum set supply temperature Max T-supply.

Heating circuit 1/2-continued

Level 4 - SPECIALIST - Description of parameters and settings - continued