beautypg.com

REMKO Multi-talent User Manual

Page 29

background image

Designation

Value range

Factory setting

Description

Cooling mode

On/Off

On

Enabling the operating mode cooling and the required settings.

F15 function

(only for CMF 80,

90,140,150,

CMT 100,150 und

EMF/EMT 100/150)

00-09

09

Setting the sensor function for sensor 15.

00 = Room sensor for heating circuit 2.
If in this position an additional sensor is recognised at the
impulse input (IMP = sensor 17), an FBR at sensors 15 and
17 will be analysed. If sensor 17 is occupied by another
function, an FBR will be analysed at sensor 15.

01 = 0-10V input for default of an external collector target
temperature.

02 = Light sensor (no function).

03 = 0-10V input for default of an external modulation depth.

04 = Second sensor for MF - function.

05 = Tank 3 (e.g. swimming pool).

06 = Sequence/priority switching (e.g. for sequence heat
pumps - conventional heating appliances).
Open contact: WE sequence 1 is active.
Short circuit against ground: WE sequence 2 is active.

07 = Locking the heat pumps (e.g. energy supply provider
contact).
Open contact: Heat pumps are enabled.
Short circuit against ground: Heat pumps are locked and the mes-
sage "energy supply provide shut-off" appears in the display.

08 = Collective fault heat pumps.
Open contact: Heat pumps are enabled.
Short circuit against ground: Fault in all heat pumps (fault
message, locking of the heat pumps and the corresponding
WE-pumps following termination of the pump run-on).

E1 function

Signal processing

(Energy supply

provider disable/

enable)

00-03

02

For heat pumps:
EMF/EMT100/150
CMF/CMT 120
CMF/CMT 160
CMF 320 Duo

00 = No function.

01 = Sequence/priority switching (e.g. for sequence heat
pumps – conventional heating appliances).
230V at E1/E2: WE sequence 1 is active.
No phase at E1/E2: WE sequence 2 is active.

02 = Locking the heat pumps (energy supply provider dis-
able).
230V at E1: Heat pumps are enabled.
No phase at E1: Fault of the heat pump and display “energy
supply provider shutdown” as well as the red indicator lamp.

03 = Collective fault heat pumps.
230V at E2: Heat pumps are enabled.
No phase at E2: Fault of the heat pump and display “Heat
pump fault” as well as the red indicator lamp.

E2 function

Signal processing

Collective fault out-

door unit and

flow monitor

00-03

03

For heat pumps:
EMF/EMT100/150
CMF/CMT 120
CMF/CMT 160
CMF 320 Duo

Sensor

1k/5k sensors

5k sensors

Setting of the available resistor parameter for the connected
sensor (NTC).

Configuration - continued

Level 4 - SPECIALIST - Description of parameters and settings - continued

29