Remko heat pump manager – REMKO Multi-talent User Manual
Page 42
REMKO HEAT PUMP MANAGER
Solar / MF
Designation
Value range
Factory setting
Description
MF 1 function
(Output A8
enable 2nd heating
appliance)
00-36
00
- Outputs
Function selection for the MF - relay (programmable multi-
function outputs).
A sensor 1-4 (sensors 11-14) can be assigned to the MF-
relay 1-4.
If an additional sensor is necessary for a specific function,
this is to be connected as sensor 15.
• 00 = not MF - function.
• 01 = collector pump.
ON: In the event of a heat demand from a user.
OFF: In the event of no heat demand from a user.
• 02 = circulation (time).
Switching the relay in accordance with the time programme
for the circulation pump.
• 03 = supply pump.
ON: In the event of a heat demand from an internal user.
OFF: In the event of no heat demand from an internal user.
A pump lag takes place.
• 05 = pump heat generator 1 (heat pump).
The multifunction output switches parallel to the heat
generator 1 (heat pump) output with an after-run time of 5
min.
• 06 = pump heat generator 2.
The multifunction output switches parallel to the heat gen-
erator 2 (heat pump) output with an after-run time of 5 min.
• 07 = switch valve tank 2 (buffer).
The valve switches the solar output of the hot water tank
to the storage tank if a collector can no longer feed into the
hot water tank.
• 08 = switch valve tank 3 (swimming pool).
The valve switches the solar output of the storage tank to
the tank 3 (sensor 15) if a collector can no longer feed into
the storage tank (the F15 function must be positioned at 5).
• 09 = switch valve tank 3 (swimming pool, only for systems
without solar trickle charging).
The valve switches the solar output of the hot water tank to
tank 3 (sensor 15) if a collector can no longer feed into the
hot water tank
(the F15 function must be positioned at 5).
• 10 = pump heat generator 3.
The multifunction output switches parallel to the heat
generator 3 (heat pump) output with an after-run time of 5
min.
• 11 = pump heat generator 4.
The multifunction output switches parallel to the heat gener-
ator 4 (heat pump) output with an after-run time of 5 min..
MF 2 function
(Output A9
Charging pump
indoor unit)
00-36
18
MF 3 function
(Output A10
Switch valve cool-
ing)
00-36
34
MF 4 function
(Output A12
solar pump
or charge pump
solid fuel boiler or
circulation pump,
sensor F14)
00-36
system selection
Level 4 - SPECIALIST - Description of parameters and settings - continued
42