Designation

Value range

Factory setting

Description

E 1 function

00-03

02

Description see specialist

configuration.

E 2 function

00-03

03

F 15 function

00-08

07

Description see specialist

configuration.

Return offset

-5.0K-15.0K

0.0K

Setting the return offset temperature.
The heat pump is only switched off after a request if the
value in sensor 17 [collector target temperature–return
offset] has been reached..

Min T-WW WE

0.0°C-90.0°C

45.0°C

Setting the minimum hot water temperature only for heat
pump operation.

Only the heat pump works until the temperature is reached
in the storage tank or drinking water tank [sensor 06]..

Min T-PU WE

0°C-90°C

0. 0 °C

Setting the minimum buffer temperature for heating
generators (not relevant for REMKO).

Until the temperature set here has been reached in the
buffer tank [sensor 02], only the heat pump will be operated
during the trickle charging.

Max WE idle time

5-210 min

45

Setting the maximum idle time for heating generators (clock
protection).
When conventional heating appliances are locked, these are
enabled again at the end of the time period set here above
the bivalence point until the target value in the collector
[sensor 08] has been reached.

Cooling mode

Designation

Value range

Factory setting

Description

T-RL cooling

10.0°C-25.0°C

15.0°C

Setting the maximum return temperature in cooling mode.

For a cooling request, the heat pump is switched on if the
temperature in the return as set here [sensor 17] is exceeded
(operating mode "Cooling" must be active).

The heat pump switches off if the temperature in sensor 17
falls below the temperature set here by 2K.

Cooling Off for WW

On/Off

On

The cooling operation is interrupted with activation of the
water heating.

Cooling with WP

00(Off)/01(On)

01

The heat pump shuts off if the signal "WP-lock" or "WP-
fault" are present at the inputs F15, E1 or E2 (=01/ON).

The chillers are regulated by the return temperature T-return (switching hysteresis 2K).

Heat pump - continued

Level 4 - SPECIALIST - Description of parameters and settings - continued

With a WW target temperature up to 50°C, the Min. T-WW WE parameter can remain set at 45°C.
If a WW target temperature in excess of 50°C is selected, the Min. T-WW WE parameter must be set to 48°C.
For energy-conservation reasons, a WW target temperature of 45°C is recommended.

NOTE

35