Remko heat pump manager – REMKO Multi-talent User Manual
Page 50
REMKO HEAT PUMP MANAGER
0000
F17
V
A
B
AB
M
M
F9
1)
2)
2)
l/h
Tmax
F8
F6
F11
F5
Designation
Value range
Programming
Output/level
00 – 9950 kW
WE 1 level 1 = 50
WE 2 level 1 = 1
WE 3 level 1 = 1
continue with key next to "End"
MF 1 function
0 0 - 3 6
0 0
T - MF 1 target
- 2 0 °C - 9 0 °C
( ---- )
MF 1 Hyst
2 K - 1 0 K
( ---- )
MF 1 Hyst Off
2 K - 1 0 K
( ---- )
MF 2 function
0 0 - 3 6
18
T - MF 2 target
- 2 0 °C - 9 0 °C
( ---- )
MF 2 Hyst
2 K - 1 0 K
( ---- )
MF 2 Hyst Off
2 K - 1 0 K
( ---- )
MF 3 function
0 0 - 3 6
1 0
T - MF 3 target
- 2 0 °C - 9 0 °C
( ---- )
MF 3 Hyst
2 K - 1 0 K
( ---- )
MF 3 Hyst Off
2 K - 1 0 K
( ---- )
MF 4 function
0 0 - 3 6
0 2
T - MF 4 target
- 2 0 °C - 9 0 °C
( ---- )
MF 4 Hyst
2 K - 1 0 K
( ---- )
MF 4 Hyst Off
2 K - 1 0 K
( ---- )
F15 function
0 0 - 0 8
0 7
E 1 function
0 0 - 0 3
0 2
E 2 function
0 0 - 0 3
0 3
Sensor
1k/5k sensors
5k sensors
Designation
Value range
Programming
BUS code BM
Off, 00-15
Off
Language
D/GB/F/NL/E/I
D (German)
Terminal address
On/Off
On
Time
0-24
Set time
Date
Year, month, day
Set date
BUS code 1
00-15
01
BUS code 2
00-15
02
System selection
---/01-12
03
Regulator type
00-06
06
WE 1 type
00-09
07
WE bus
00-05
05
Gradient
On/Off
Off
WE 2 type
00-22
01
WE 2 tank
00-03
00
WE 3 type
00-09
01
WE 4 type
00-09
00
Buffer type
00-02
00
Cooling mode
Off/On
Off
HC1 function
Standard, T-feed
const, swimming
pool, WW,
return
Standard
HC2 function
see HC1
Standard
Hydraulic diagram for the heat pump assembly 2 (only for CMF 80/140)
Functions: Heating and hot water,
bi-fuel operating mode with gas wall mounted heater
“System selection 3”
Outdoor unit
Indoor unit
CMF80/140
Process water
Storage tank
HPS 500
Heating/cooling
water
Storage tank
KPS 300
Heating circuit 1 Heating circuit 2
4)
Notes:
1) Recommended location for heat meters.
We recommend a set-up with a flow volume of 2.5 m
3
/h.
2) Heating circuit circulation pump(s) not included in REMKO's scope of delivery. We recommend the use of high-efficiency circulation pumps.
4) If the surface heating is the only heat distribution system, it automatically becomes a heating circuit 1. A mixer is not necessary in this case!
Taps
CW inlet
Fresh water station
Gas wall
mounted heater.
Sample hydraulic diagram for system selection 3