REMKO Multi-talent User Manual
Page 23
Designation
Description
Software number
Display of the software number with index.
Manual cascade operation
Only for cascades; the operating mode Service must be activated.
Setting the heating appliance's output (For a switching, multi-level WE, the second level can be
switched on with a performance target of > 50%).
Inputs are automatically reset when the Service function is ended.
Burner running-time
Display of the heating appliance running time for all levels.
Burner starts
Display of the heating appliance starts for all levels.
STB test
Safety temperature limiter test with display of the temperature for the WE. (Start with the F-key)
Customer service
Input of the date for the annual maintenance reminder (at Year = "00" no reminder) or input of the
running time for the system after which a maintenance reminder should generate
(for running time < "50" no reminder).
Reset user
Respective areas can be reset to the factory setting using the reset function (factory setting = "01").
Reset specialist
Reset time programme
Communication BM 1
Remote control HC 1 at the BUS.
Communication BM 2
Remote control HC 2 at the BUS.
Communication KM
Communication with expansion module (for additional heating circuits).
Additional entries
Relay test
Select the desired relay using the rotary knob at the service level (01-11)
The selected relay is switched on for 1 minute and all other relays are switched off.
Please note that the input of the code number is required for this function.
The relay test breaks off automatically after 5 minutes if no further operation takes place.
Relays Output
Description
00
Normal operation => relays switch in accordance with the regulating function
01
A1
Circulation pump heating circuit 1 (direct heating circuit) on
02
A2
Circulation pump heating circuit 2 (mixer circuit) on
03
A3
Switch valve/charge pump DHW
04
A4
Mixer heating circuit 2 open
05
A5
Mixer heating circuit 2 closed
06
A6
Enable heat pump on (charge pump run parallel)
07
A7
For EMF/EMT 100/150;CMF/CMT 120/160: Enable cooling
For CMF 80/140: 2. Heating appliance on
For CMF 90/150 and CMT100/150 circulation pump cooling on
08
A8
Enable 2nd heating appliance (multi-function 1-output)
09
A9
Charge pump inside unit (multi-function 2-output)
10
A10
For CMF 80/90: Condenser pump
For CMF/CMT 120/160, EMF/EMT 100/150, CMF 90/150, CMT 100/150:
Switch valve cooling (multi-function 3-output)
12
A12
Circulation pump or solar pump or charge pump UP-solid fuel boiler
(Multi-function 4-output)
Level 4 - SERVICE - Description of parameters and settings - continued
23