REMKO Multi-talent User Manual
Page 27
Configuration - continued
Designation
Value range
Factory setting
Description
WE BUS
00-05
05
• 00 = Relay (switching heat generator).
• 01 = CAN-BUS (cascade switching).
• 02 = eBUS (heat generator without temperature controller,
default modulation depth, cascade modulating).
• 03 = eBUS (heat generator with temperature controller,
default target temperature T-WE target).
• 04 = 0-10V (default target temperature T-WE target,
burner relays are controlled in parallel).
Only for regulation type 01, 02, 03, 07.
Sensor 08 must be connected.
• 05 = 0-10V (default modulation depth).
Only for regulation type 02 or 06.
T-collector [sensor 08] must be connected.
WE 2 type
(Output A7
enable cooling)
00-22
08
Not active for heat generator 1 with two stage burner.
• 00 = no second heat generator.
• 01 = Single stage heat generator (switching).
• 07 = Heat pump.
• 08 = Cooling 1.
• 09 = Cooling 2.
• 20 = Solid fuel boiler (supplemental not controllable heat
generator).
• 21 = Collector pump
• 22 = Pump for heat generator 1 (e.g. supplemental heat
generator for cascades).
WE 2 tank
00-03
00
Only active if heat generator 2 type as solid fuel boiler was
selected.
Start-up release:
ON: T-WE 2 > Min T-WE 2.
OFF: T-WE 2 < [Min T-WE 2-5K].
• 00 = Heating in countercurrent with collector (no tank)
[sensor 08].
ON: T-WE 2 > [T-collector+Hyst burner 2+5K].
OFF: T-WE 2 < [T-collector+Hyst burner 2].
• 01 = Heating in countercurrent with buffer tank [sensors
01, 03].
ON: T-WE 2 > [T-buffer O+Hyst burner 2+5K].
OFF: T-WE 2 < [T-buffer+Hyst burner 2].
• 02 = Heating in countercurrent with warm water tank
[sensor 06].
ON: T-WE 2 > [T-WW+Hyst burner 2+5K].
OFF: T-WE 2 > [T-WW+Hyst burner 2].
• 03 = Heating in countercurrent with tank 3 (swimming
pool) [sensor 15].
ON: T-WE 2 > [T-tank 3+Hyst burner 2+5K].
OFF: T-WE 2 < [T-tank 3+Hyst burner 2].
Level 4 - SPECIALIST - Description of parameters and settings - continued
27