REMKO Multi-talent User Manual
Page 31
Designation
Value range
Factory setting
Description
Hyst burner 2
2.0K-20.0K
2.0K
Only for two stage burners or solid material integration.
Setting the hysteresis for the charge pump (solid material
integration) or the 2nd burner
Gradient
On/Off
Off
Activation or deactivation of the gradient-based algorithm.
At „OFF“, the shut-off of the heat pump is carried out by
the target value and the hysteresis.
This function is only assigned to heat generator 1, in other
words the heat pump, and must be set to OFF.
Max reduction
1.0K-20.0K
1.0K
Setting the value to determine the earliest shut-off point
with the gradient-based algorithm activated.
The earliest shut-off point is the difference between the
maximum heating appliance temperature Max T-WE
(see specialist cascade) and the value set here.
Dyn shut-off
0.5K/min.-10K/
min.
2.0K/min.
Load dependent, early shut-off of the heat generator by the
the temperature increase gradients [K/min].
If the heat generator reaches or exceeds the gradient set
here, the heat generator will be switched off at the earliest
dynamic shut-off point (difference between Max T-WE and
Max reduction).
At a low temperature increase, the shut-off point will be in-
creased linearly up to Max T-WE.
WE cooling function
On/Off
Off
Activating the emergency cooling for the heat generator.
T-WE cold start
30.0°C-120.0°C
95.0°C
Setting the maximum temperature for the heating appliance
(Cooling start temperature).
If emergency cooling for the heating appliance has been ac-
tivated (heat generator cooling function = ON), the heating
circuits will then be taken with
Max T-supply (see specialist
heating circuit 1/2) into
operation (if emergency cooling is permitted in the heating
circuit), as soon as the temperature set here has been ex-
ceeded by one of the heating appliances.
Emergency cooling is ended if the start temperature T-WE
cold start is undercut by 5K.
Heating appliances - continued
Level 4 - SPECIALIST - Description of parameters and settings - continued
31