Remko heat pump manager – REMKO Multi-talent User Manual
Page 38
REMKO HEAT PUMP MANAGER
Designation
Value range
Factory setting
Description
Hysteresis WW
3. 0 K - 3 0. 0 K
5. 0 K
Setting the hot water hysteresis.
Water heating starts if the temperature in the hot water tank
(sensor F-6) falls below the target temperature (see user
hot water
T-WW target) by the temperature set here.
Water heating ends if the tank reaches the set target
temperature
(in the anti-legionella mode the target temperature is set to
65°C, see user
hot water
anti-legionella).
WW lag
0 0 - 3 0
0 1
Setting the pump lag period.
The pump lag period (5 min.) is extended by the value set
here.
The indoor unit's charge pump continues to run for
another 5 minutes after the heat pump has been shut off
(independent of the period set here).
The lag period is interrupted if there is a demand for heat in
a heating circuit.
An activated charge pump lock can likewise lead to an
interruption of the lag function.
TH inlet
On / Off
Off
Activating the water heating by means of thermostat or sensor.
• On (water heating by means of thermostat)
In the event of a short circuit, water heating is started at the
tank sensor's connection terminals. It ends if the short circuit
has been corrected.
• Off (water heating by means of tank sensor).
Thermal function
On / Off
Off
Activating the aligned target temperature.
The target temperature during water heating is arrived at by
adding the current tank temperature [sensor 6] to T-WE WW.
Charging
On / Off
Off
Activating the charging function
(only possible with sensor 12 = T-WW U).
Water heating with activation of this function (charging =
ON) is not ended until the sensor F 12 (not F 6) has reached
the warm water target temperature.
Hot water - continued
Level 4 - SPECIALIST - Description of parameters and settings - continued
38