Remko heat pump manager – REMKO Multi-talent User Manual
Page 26
REMKO HEAT PUMP MANAGER
Configuration - continued
Designation
Value range
Factory setting
Description
System selection
----/01-12
01
With the selection of the system, one of the 12 basic hy-
draulic configurations described below is loaded; they are
saved in the heat pump manager. With this pre-configura-
tion, the additional values to be set are minimised for the
installer.
The basic hydraulic configurations, including parameter val-
ues, can be found in the appendix of this manual..
• 01 = Basic hydraulics for the functions “Heating and hot
water”, single energy-source mode, 1 supplemental electric
heating, bivalence point -5°C
• 02 = only heating version, single energy-source mode,
2 levels for supplemental electric heating, bivalence point -5°C.
• 03 = only heating version, bivalent mode, boiler + option
for 1 supplemental electric heating, bivalence point -3°C.
• 04 = only heating version, bivalent mode, solid fuel boiler
+ option for supplemental electric
Supplemental heating, bivalence point -3°C.
• 05 = only heating version, single energy-source mode,
1 supplemental electric heating, solar system, bivalence point -5°C.
• 06 = only heating/cooling version, single energy-source
mode, 1 supplemental electric heating, bivalence point -5°C.
• 07 = only heating/cooling version, single energy-source
mode, 1 supplemental electric heating, solar system,
bivalence point -5°C.
• 08 = only heating version, single energy-source mode,
2 levels for supplemental electric heating, solar system,
bivalence point -5°C.
• 09 = only heating version, bivalent mode + option for 1
supplemental electric heating, solar system, bivalence point -3°C.
• 10 = only heating/cooling version, bivalent mode,
bivalence point -3°C
• 11 = heating/cooling version, bivalent mode, solar system,
bivalence point -3°C
• 12 = heating/cooling version, bivalent mode with solid fuel +
option for 1 supplemental electric heating, bivalence point -3°C
There is no change for "----"
Notice: The selections of the system 02,03,04,05,08 and 09 is
are only for heat pumps CMF 80 and CMF 140..
Regulator type
00-06
06
Setting the regulation type for the system.
• 00 = No heating appliance (mixer expansion).
• 01 = Single stage heat generator (switching).
• 02 = Single stage (modulating).
• 03 = Two stage heat generator (switching).
• 04 = Two individual heat generator (switching).
• 05 = Multi-level switching (cascade over BUS).
• 06 = Multi-level modulating (cascade over BUS).
WE 1 type
(Output A6
enable or demand
heat pump)
00-09
07
• 00 = Relay has no function.
• 01 = Switch on heat generator.
• 07 = Switch on heat pump.
• 08 = Switch on cooling 1.
• 09 = Switch on cooling 2.
Level 4 - SPECIALIST - Description of parameters and settings - continued
26