Remko heat pump manager – REMKO Multi-talent User Manual
Page 16
REMKO HEAT PUMP MANAGER
Hot water
Designation
Value range
Factory setting
Description
1xhot water
On/Off
Off
The tank is only enabled for a one time loading
(= ON) (e.g. for showering outside of hot water times).
Loading only begins if the T-WW 1 target temperature has
been undercut by the amount of the switching hysteresis
(see specialist
hot water
hysteresis WW)
.
.
T-WW 1 target
10°C-70°C
50°C
Setting the desired hot water temperatures for the hot water
programme's 1st, 2nd and 3rd enabling times (see time
programme
hot water).
T-WW 2 target
10°C-70°C
50°C
T-WW 3 target
10°C-70°C
50°C
BoB value
0.0K-70.0K
0.0K
Power saving function for solar or solid fuel boiler (operation
without burner).
The burner is activated if the current hot water temperature
in the amount of the set value here + switching hysteresis
(see specialist
hot water
hysteresis WW) has fallen
below the set hot water target temperature.
Circ with WW prog
On/Off
Off
Activating the circulation pump.
The circulation pump runs when hot water is enabled
(= ON), the circulation programme (see time programme
circulation programme) has no impact.
Anti-legionella
On/Off
Off
Activating the anti-legionella function.
With every 20th heating or at least once a week (on
Saturdays at 01:00) the tank is warmed to 65°C (= ON).
It is possible to set a separate anti-legionella function e.g.
by means of the 3rd hot water enabling time (see time
programme
hot water).
Be submitted to activation of anti-legionella program must
usually electric heating thermostat to 65 °C.
Heating circuit 1/2
Designation
Value range
Factory setting
Description
Operating mode
----
Standby
Cooling
Automatic 1+2
Summer
Heating
Reduction
Service
----
Setting the operating mode for the respective heating circuit.
!
CAUTION
If an operating mode is set here outside of "----", this
operating mode will always apply for the respective heating
circuit regardless of the operating mode setting in the main
menu. This setting possibility is intended for the use of a
remote control.
T-room target 1
5.0°C-40.0°C
20.0°C
Setting of the desired room temperature for the 1st, 2nd
and 3rd enabling times of the active heating programme in
automatic 1/2 operating mode. A setting other than 20 °C
causes a parallel shift of the heat curve on page 6.
T-room target 2
5.0°C-40.0°C
20.0°C
T-room target 3
5.0°C-40.0°C
20.0°C
T-reduction
5.0°C-40.0°C
15.0°C
Setting the desired room temperature during night reduction
(time between heating periods, see time programme
heating circuit 1/2 prog 1/2).
Adjustable values can vary depending on the function selected for the heating circuit.
Level 4 - USER - Description of parameters and settings - continued