beautypg.com

REMKO Multi-talent User Manual

Page 45

background image

Designation

Value range

Factory setting

Description

MF 4 Hyst

2.0K-10.0K

5.0K

Setting the MF 4 hysteresis.

MF 4 Hyst Off

2.0K-10.0K

2.0K

Setting the MF 4 hysteresis for the shut-off process.

Max T-supply

80.0°C-180.0°C

110.0°C

Setting the maximum collector temperature.

The collector pumps lock if the corresponding collector

temperature rises above the temperature set here (system

protection).

The pumps are enabled again if the collector temperature

falls below the temperature

[Max T-solar-10K].

Min T-solar on

-20.0°C-95.0°C

50.0°C

Setting the minimum collector temperature.

The collector pump is enabled if the corresponding collector

temperature rises above the temperature set here.

Min T-solar off

-15.0°C-95.0°C

45.0°C

Setting the minimum locking temperature for the collector

pump.

The collector pump locks if the corresponding collector

temperature falls below the temperature set here.

This function prevents the pump from operating without

relevant heat output.

T-solar protection

80.0°C-180.0°C

110.0°C

Setting the collector protection temperature.

The collector protection function protects the collector

against overheating. If the collector temperature exceeds the

temperature set here and the tank temperature is less than

92°C, the tank will be charged in excess of its maximum

temperature up to 95°C to cool the collector.

The function is interrupted if the collector exceeds its

maximum temperature.

The function is enabled again if the collector temperature

falls below the maximum temperature-3K.

Solar/MF - M 4 function - continued

Level 4 - SPECIALIST - Description of parameters and settings - continued

Description

31 = Reloading pump storage tank 2.
The F15 function must be at the position 4.
The relay switches if the temperature of the storage tank
rises above the temperature sensor 15 by the amount of the
hysteresis MF hyst.
It shuts off if the temperature falls below the temperature
[F15 + MF hyst Off].

32 = direct heating circuit.
Heating circuit with fixed supply temperature (T-MF target).
In the event of a short circuit at the assigned MF-sensor
(over room thermostat/time switch) the heating circuit
pump switches ON and the supply target temperature for
the heat generator is defined.
The pump experiences a lag period after the sensor short
circuit has been corrected.

Description

33 = thermostat function.
ON: T-MF > T-MF target.
OFF: T-MF < [T-MF target-MF hyst].

34 = bypass valve cooling mode.
The relay switches in the cooling mode
(Separating the conventional heat generator from the cool-
ing circuit and water heating is possible during the cooling
operation). The MF-sensor captures the supply temperature
for the heat generator-regulation.

35 = bypass valve cooling mode invers.
The relay is switched in the opposite direction to function 34.

Solar/MF - continued

45