Appendix d - vcc-x bacnet, Vcc-x bacnet, Parameters – Orion System VCC-X Controller User Manual
Page 98: Vcc-x controller technical guide 98
APPENDIX D - VCC-X BACnet
®
VCC-X Controller Technical Guide
98
VCC-X BACnet
®
Parameters
BACnet
®
Properties for the VCC-X Controller
Parameter
Object
Description
Limits
Compressor
A1 Suction
Pressure
AI:40
Current compressor A1
Suction Pressure
Compressor
A1 Head
Pressure
AI:41
Current compressor A1
Head Pressure
Compressor
A1 Coil
Temperature
AI:42
Current compressor A1 Coil
Temperature
Compressor
A1 Superheat
AI:43
Current compressor A1
Superheat Temperature
Refrigeration
Module #1
AI 5
AI:44
Future Input Status for
Analog Input #5
Compressor
A2 Coil
Temperature
AI:45
Current compressor A2 Coil
Temperature
Compressor
A2 Superheat
AI:46
Current compressor A2
Superheat Temperature
Compressor
B1
Signal
AI:47
Compressor B1 Modulating
Cooling Signal
Compressor
B1 Condenser
AI:48
Current percentage of the
B1 Condenser Signal
Compressor
B1 Suction
Pressure
AI:49
Current compressor B1
Suction Pressure
Compressor
B1 Head
Pressure
AI:50
Current compressor B1
Head Pressure
Compressor
B1 Coil
Temperature
AI:51
Current compressor B1 Coil
Temperature
Compressor
B1 Superheat
AI:52
Current compressor B1
Superheat Temperature
Refrigeration
Module #2
AI 5
AI:53
Future Input Status for
Analog Input #5
Compressor
B2 Coil
Temperature
AI:54
Current compressor B2 Coil
Temperature
Compressor
B2 Superheat
AI:55
Current compressor B2
Superheat Temperature
Compressor
C1
Signal
AI:56
Compressor C1 Modulating
Cooling Signal
Compressor
C1 Condenser
AI:57
Current percentage of the
C1 Condenser Signal
Compressor
C1 Suction
Pressure
AI:58
Current compressor C1
Suction Pressure
BACnet
®
Properties for the VCC-X Controller
Parameter
Object
Description
Limits
Compressor
C1 Head
Pressure
AI:59
Current compressor C1
Head Pressure
Compressor
C1 Coil
Temperature
AI:60
Current compressor C1 Coil
Temperature
Compressor
C1 Superheat
AI:61
Current compressor C1
Superheat Temperature
Refrigeration
Module #3
AI 5
AI:62
Future Input Status for
Analog Input #5
Compressor
C2 Coil
Temperature
AI:63
Current compressor C2 Coil
Temperature
Compressor
C2 Superheat
AI:64
Current compressor C2
Superheat Temperature
Compressor
D1
Signal
AI:65
Compressor D1 Modulating
Cooling Signal
Compressor
D1 Condenser
AI:66
Current percentage of the
D1 Condenser Signal
Compressor
D1 Suction
Pressure
AI:67
Current compressor D1
Suction Pressure
Compressor
D1 Head
Pressure
AI:68
Current compressor D1
Head Pressure
Compressor
D1 Coil
Temperature
AI:69
Current compressor D1 Coil
Temperature
Compressor
D1 Superheat
AI:70
Current compressor D1
Superheat Temperature
Refrigeration
Module #4
AI 5
AI:71
Future Input Status for
Analog Input #5
Compressor
D2 Coil Temp.
AI:72
Current compressor D2 Coil
Temperature
Compressor
D2 Superheat
AI:73
Current compressor D2
Superheat Temperature
Alarm Status
AI: 74
Indicates an alarm
condition.
See Alarm
Group Bits on
page 107.
Preheater
Leaving Air
Temp #1
AI: 75
Current Preheater
Leaving Air Temperature #1
Preheater
Leaving Air
Temp #2
AI: 76
Current Preheater
Leaving Air Temperature #2
Preheater
Entering Air
Temp
AI: 77
Current Entering Air Temp
for Preheater