VCC-X CONTROLLER WIRING

VCC-X Controller Technical Guide

34

Supply Fan VFD Wiring

24VAC

GND

Line
Voltage

Size Transformer For
Correct Total Load.
VCC-X Controller = 15 VA

VCC-X Controller

+

Supply Fan Variable Frequency Drive

(By Others)

_

0-10VDC Input From AOUT1

GND

Caution:

The VFD Unit Must Be Configured For 0-10

VDC Input. The Input Resistance At The VFD Must Not
Be Less Than 1000 Ohms When Measured At The VFD
Terminals With All Input Wires Removed.

Note:

Wire To The VFD Using 18 GA

Minimum 2 Conductor Twisted Pair
With Shield Cable. Wire Shield To GND
As Shown.

AOUT1

GND

Shield

Figure 19: Supply Fan VFD Wiring

Supply Fan VFD Signal

The Supply Fan VFD Signal is a user-adjustable signal with a range
of 0-10 VDC from AOUT1 on the VCC-X Controller. This signal
output can be connected to the Supply Fan Variable Frequency Drive
to modulate the Supply Fan speed.

See Figure 20 below for detailed wiring.

CAUTION:

Variable Frequency Drive units can cause large

transient noise spikes which can cause interference to be

propagated on other electronic equipment. Use shielded wire

wherever possible and route all sensor and controller wiring

away from the Variable Frequency Drive and the HVAC Unit

electrical wiring.