beautypg.com

Appendix d - vcc-x bacnet, Vfd test screens & address screen, Vcc-x controller technical guide – Orion System VCC-X Controller User Manual

Page 95: 95 vfd test screens, Address screen

background image

VCC-X Controller Technical Guide

APPENDIX D - VCC-X BACnet

®

95

VFD Test Screens

Refer to the following map when navigating through the VFD Test
Screens. VFD test screens are only used when VFD is connected
via MODBUS communications. From the VFD TEST Screen, press

to scroll through the screens.

VFD TEST

ENABLED/

DISABLED

VFD COMPRESSOR TEST

Values are Enable or Disabled.

VFD FREQ

0.0 HZ

VFD COMPRESSOR FREQUENCY

Current VFD Frequency. Values are 0.0 HZ to

VFD VOLT

0.0

VFD COMPRESSOR VOLTAGE

Current VFD Voltage.

VFD AMPS

0

VFD COMPRESSOR AMPS

Current VFD Amps.

Address Screen

ADDRESS

1(152)

CURRENT BOARD ADDRESS

Confi gure the address according to which refrigerant circuit

this module represents—1=A, 2=B, 3=C, 4=D.

Number in parentheses is E-BUS address.

VFD Test Screens & Address Screen

This manual is related to the following products: