VCC-X Controller Technical Guide
APPENDIX D - VCC-X BACnet
®
97
VCC-X BACnet
®
Parameters
BACnet
®
Properties for the VCC-X Controller
Parameter
Object
Description
Limits
Application
Software
Version
AI: 1
Current version of the
software in the unit.
Control Mode
AI:2
Confi gured unit application.
See Control
Mode Bits on
page 107.
Control Status
AI: 3
Current Occupied/
Unoccupied Status.
See Control
Status Bits on
page 107.
HVAC Mode
AI: 4
Current operational status.
See HVAC
Mode Bits on
page 107.
Control
Temperature
AI: 5
Current value of the Control
Temperature Sensor.
Cooling
Setpoint
AI: 6
Occupied Cooling Mode
Enable Setpoint Mirror.
Heating
Setpoint
AI: 7
Occupied Heating Mode
Enable Setpoint Mirror.
Sensor Slide
Adjust Effect
AI: 8
Amount Of Current Sensor
Slide Offset
Supply Air
Temperature
AI: 9
Current value of the
Supply Air
Temperature sensor
Supply Air
Setpoint
AI: 10
Current SAT Cooling or
Heating Setpoint if there is
no reset source; Current
calculated SAT setpoint
with Reset Source
Coil
Temperature
Setpoint
AI: 11
This is the current
calculated Coil Suction
Temperature target during
Dehumidifi cation Mode.
Space
Temperature
AI: 12
Current value of the Space
Temperature Sensor.
Space
Humidity
AI: 13
Current value of the Space
Humidity.
Return Air
Temperature
AI: 14
Current value of the Return
Temperature Sensor.
Return Air
Humidity
AI: 15
Current value of the Return
Air Humidity.
Outdoor Air
Temperature
AI: 16
Current value of the
Outdoor
Temperature Sensor.
Outdoor Air
Humidity
AI:17
Current value of the
Outdoor Humidity Sensor.
Outdoor Air
Wetbulb
Temperature
AI:18
Current calculated Outdoor
Wetbulb Temperature.
BACnet
®
Properties for the VCC-X Controller
Parameter
Object
Description
Limits
Outdoor Air
Dewpoint
Temperature
AI:19
Current Calculated Outdoor
Air Dewpoint Temperature.
SAT Setpoint
Reset Voltage
AI:20
Supply Air Temp Setpoint
Reset Input Signal
Duct Static
Pressure
AI: 21
Current Duct Static
Pressure
Duct Static
Control Signal
AI: 22
Current Duct Static Control
Signal (Fan VFD)
Building
Pressure
AI: 23
Current value of the
Building Pressure Sensor.
Building
Pressure
Control Signal
AI:24
Current Building Pressure
Control Signal
Outdoor
Airfl ow
AI: 25
Current Outdoor Airfl ow
Measurement.
Supply
Airfl ow
AI: 26
Current Supply Airfl ow
Measurement.
Return
Airfl ow
AI: 27
Current Return Airfl ow
Measurement.
Exhaust
Airfl ow
AI: 28
Current Exhaust
Airfl ow Measurement
CO
2
AI: 29
Current Indoor
CO
2
Level.
Economizer
Position
AI: 30
Current Modulating Signal
to the Economizer Damper.
Title 24
Economizer
Feedback
AI: 31
Current position of feedback
from Economizer actuator.
Return Air
Damper
AI: 32
Current Signal to the Return
Air Damper if using Return
Air Bypass.
Return Bypass
Damper
AI: 33
Current Signal to the Return
Air Bypass Damper if using
Return Air Bypass.
Modulating
Cooling
Position
AI: 34
Current percentage of the
Modulating Cooling Signal
(Chilled Water or Digital
Compressor).
Modulating
Heating
Position
AI: 35
Current percentage of the
Modulating Heating signal
(Hot Water or SCR heat).
Reheat Valve
Position
AI: 36
Current position of
MHGRV Modulating Hot
Gas Reheat Valve.
Modulating
Gas Valve
Position
AI: 37
Current position of
MODGAS Modulating Gas
Valve Control.
Compressor
A1 Signal
AI:38
Compressor A1 Modulating
Cooling Signal
Compressor
A1 Condenser
AI:39
Current percentage of the
A1 Condenser Signal
NOTE:
When using Celsius scaling, all temperature values will
need to be divided by 10 by the BMS to properly read
the status and setpoint values, e.g., a value of 200º C
needs to be divided by 10 for an actual value of 20º C.