beautypg.com

Vcc-x expansion module 1 wiring, Return air bypass wiring, Vcc-x controller technical guide – Orion System VCC-X Controller User Manual

Page 43: Return air bypass, Vcc-x em1 expansion module, Figure 28: return air bypass wiring, The vcc-x controller can be confi gured for aaon, Line voltage

background image

VCC-X Controller Technical Guide

VCC-X EXPANSION MODULE 1 WIRING

43

Figure 28: Return Air Bypass Wiring

Return Air Bypass Wiring

Return Air Bypass

The VCC-X Controller can be confi gured for AAON

®

Return Air

Bypass applications. These provide improved moisture removal
capabilities while utilizing internal space loads for reheat by
redirecting Return Air around the Evaporator Coil instead of through
the coil. See the AAON

®

Return Air Bypass application section of

this manual on page 6 for complete operation details.

The AAON

®

Return Air Bypass applications utilize a Return Air

Bypass Damper Actuator and a Return Air Damper Actuator to
modulate the Return Air and Return Air Bypass Dampers to control
the amount of air that is redirected around the Evaporator Coil.

See Figure 28 below for detailed wiring of the Return Air Bypass
and Return Air Damper Actuators.

WARNING: It is very important to be certain that all wiring

is correct as shown in the wiring diagram below. Failure to

observe the correct polarity could result in damage to the

Damper Actuator or the VCC-X Expansion Module.

VCC-X EM1
Expansion Module

WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-
24VAC. Failure to observe polarity will result in damage to one or more of the
boards. Expansion Modules must be wired in such a way that the expansion
modules and the controller are always powered together. Loss of power to the
expansion module will cause the controller to become inoperative until power is
restored to the expansion module.

AOUT2

24VAC

GND

Line Voltage

Size Transformer For
Correct Total Load.
VCC-X E 1 Module = 5 VA

M

GND

AOUT3

WattMaster Label

#L102196-A

Rev.: 1A

B

+24

VAC

GND

RELA

Y

C

ONT

A

CT

RA

TING

IS

1

A

MP

MAX

@

24

V

A

C

R1

R2

R3

R4

R5

RC

RELAY OUTPUT

TERMINALS

ANALOG OUTPUT TERMINALS

GND

RETURN DAMPER

RETURN BYPASS

CHILLED WATER

AOUT4

PWM –

PWM +

E-BUS

CONNECT

24 VAC POWER ONLY

WARNING! POLARITY

MUST BE OBSERVED OR

THE CONTROLLER WILL

BE DAMAGED

POWER INPUT TERMINAL BLOCK

PUT

T

VCC-X Expansion Module 1

Orion No.: OE336-23-VCCXEM1

AAON No.: V53990

RETURN AIR

DAMPER ACTUATOR

2 +

Y1

3

COM

1

RETURN AIR BYPASS

DAMPER ACTUATOR

2 +

Y1

3

COM

1

Belimo Actuator Wiring
Shown. Consult Factory
For Other Manufacturer
Wiring Instructions.