Sequence of operations, Outdoor air lockouts, system broadcasts & alarms, Vcc-x controller technical guide 66 – Orion System VCC-X Controller User Manual
Page 66: Outdoor air lockouts, System broadcasts, Alarm detection and reporting
Zone
Zone
SEQUENCE OF OPERATIONS
VCC-X Controller Technical Guide
66
Outdoor Air Lockouts, System Broadcasts & Alarms
Outdoor Air Lockouts
The compressors are disabled during Cooling Mode when the
Outdoor Air Temperature is below the Compressor Cooling Lockout
Setpoint.
Mechanical heating is disabled when the Outdoor Air Temperature
is above the Heating Lockout Setpoint.
For Air to Air Heat Pumps, the compressors are disabled during
Heating Mode when the Outdoor Air Temperature is below the
Compressor Heating Lockout Setpoint.
System Broadcasts
An Outdoor Air Temperature Sensor reading is broadcast from
any one VCC-X Controller to any controller that does not have an
Outdoor Air Temperature Sensor.
Alarm Detection and Reporting
The VCC-X Controller continuously performs self diagnostics
during normal operation to determine if any operating failures have
occurred.
These failures (alarms) can be reported to a Touch Screen System
Manager, a Hand Held Modular Service Tool, or to a computer
running Prism 2 software.
Diagnostic LEDs on the VCC-X controller will generate “blink
codes” for certain alarm conditions.
The following are the available alarm designations for the VCC-X
Controller:
Bad
SAT
Sensor
Bad
RAT
Sensor
Bad
OAT
Sensor
Bad
Space
Sensor
Bad
CO
2
Sensor
Bad Building Pressure Sensor
Missing Outdoor CFM Sensor
Missing Exhaust CFM Sensor
Missing Supply CFM Sensor
Missing Return CFM Sensor
Mechanical
Cooling
Failure
Mechanical
Heating
Failure
Fan
Proving
Alarm
Dirty
Filter
Alarm
Emergency
Shutdown
Relay
Runtime
No
Economizer
Feedback
Title 24 Economizer Air Temperature Sensor Failure
Title 24 Economizer Damper Failure
Title 24 Economizer Excess Outdoor Air
Title 24 Economizer Not Economizing When It Should
Title 24 Economizer Economizing, But Shouldn’t
High
Supply
Air
Temperature
Cutoff
Low
Supply
Air
Temperature
Cutoff
High
Control
Temperature
Low
Control
Temperature
Missing
RSM
#1
Missing
RSM
#2
Missing
RSM
#3
Missing
RSM
#4
Missing
PREHEAT-X
Missing
MHGRV-X
Missing
MODGAS-X
Missing
EM1
Missing
12RLY