SEQUENCE OF OPERATIONS

VCC-X Controller Technical Guide

66

Outdoor Air Lockouts, System Broadcasts & Alarms

Outdoor Air Lockouts

The compressors are disabled during Cooling Mode when the
Outdoor Air Temperature is below the Compressor Cooling Lockout
Setpoint.

Mechanical heating is disabled when the Outdoor Air Temperature
is above the Heating Lockout Setpoint.

For Air to Air Heat Pumps, the compressors are disabled during
Heating Mode when the Outdoor Air Temperature is below the
Compressor Heating Lockout Setpoint.

System Broadcasts

An Outdoor Air Temperature Sensor reading is broadcast from
any one VCC-X Controller to any controller that does not have an
Outdoor Air Temperature Sensor.

Alarm Detection and Reporting

The VCC-X Controller continuously performs self diagnostics
during normal operation to determine if any operating failures have
occurred.

These failures (alarms) can be reported to a Touch Screen System
Manager, a Hand Held Modular Service Tool, or to a computer
running Prism 2 software.

Diagnostic LEDs on the VCC-X controller will generate “blink
codes” for certain alarm conditions.

The following are the available alarm designations for the VCC-X
Controller:

Bad

SAT

Sensor

Bad

RAT

Sensor

Bad

OAT

Sensor

Bad

Space

Sensor

Bad

CO

2

Sensor

Bad Building Pressure Sensor

Missing Outdoor CFM Sensor

Missing Exhaust CFM Sensor

Missing Supply CFM Sensor

Missing Return CFM Sensor

Mechanical

Cooling

Failure

Mechanical

Heating

Failure

Fan

Proving

Alarm

Dirty

Filter

Alarm

Emergency

Shutdown

Relay

Runtime

No

Economizer

Feedback

Title 24 Economizer Air Temperature Sensor Failure

Title 24 Economizer Damper Failure

Title 24 Economizer Excess Outdoor Air

Title 24 Economizer Not Economizing When It Should

Title 24 Economizer Economizing, But Shouldn’t

High

Supply

Air

Temperature

Cutoff

Low

Supply

Air

Temperature

Cutoff

High

Control

Temperature

Low

Control

Temperature

Missing

RSM

#1

Missing

RSM

#2

Missing

RSM

#3

Missing

RSM

#4

Missing

PREHEAT-X

Missing

MHGRV-X

Missing

MODGAS-X

Missing

EM1

Missing

12RLY

This manual is related to the following products: