MHGRV-X CONTROLLER WIRING

VCC-X Controller Technical Guide

46



The Supply Air Temperature Reset Signal



If the communication is interrupted between the

MHGRV-X Controller and the VCC-X Controller,

the MHGRV-X controller will revert to stand-alone

operation.

For more information, refer to the MHGRV-X Controller Technical
Guide.

NOTE:

If using multiple E-BUS Sensors or Modules, the

E-BUS Hub or Adapter Board may be required.

MHGRV-X Controller Wiring

MHGRV-X Controller Wiring

The OE377-26-00059 MHGRV-X Controller (AAON part number
V12100) is designed to control a Modulating Hot Gas Reheat Valve
to maintain a desired Supply Air Temperature and Dehumidifi cation
setpoint. The MHGRV-X Controller directly connects to the VCC-
X Controller or indirectly using an E-BUS Expansion Board via an
EBC E-BUS cable. See Figure 31.

The following information will be passed between the MHGRV-X
controller and the VCC-X Controller:



Reheat Enable command



Supply Air Temperature Setpoint



The Reset Supply Air Temperature Setpoint

Figure 31: MHGRV-X Controller to VCC-X Controller Wiring

Line

GND

24V

AC

40 VA

Transformer

Minimum

Supply

Air Temperature

Sensor

Mount In Supply

Air Duct

RED

GRN

WHT

BLK

Condenser Valve #1

HGR Valve #1

RED

GRN

WHT

BLK

EBC E-BUS Cable

Connects To The

VCC-X Controller’s

Expansion Port Directly

or Indirectly Using an

E-BUS Expansion Board

Supply Air Temperature

Sensor Connects to AI3 & GND

On VCC-X Controller

MHGRV-X CONTROLLER

(OE377-26-00059)

Set Jumper To

NORMAL.

Fan

Compressor

HGR Solenoid Valve

2 Position HGR Valve (Optional)

C1

C2

COMM